Study on circuit breaker TRV issues of UHV high series compensation lines

Under the influence of series compensation (SC) capacitance and rated voltage rise, when ultra high voltage (UHV) high SC line occurs inner fault, the short-circuit current through the SC line is greater and the residual voltage across the SC is higher, which cause the electromagnetic transient proc...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Journal of engineering (Stevenage, England) England), 2019-03, Vol.2019 (16), p.867-871
Hauptverfasser: Zheng, Bin, Xiang, Zutao, Ban, Liangeng, Jiang, Hongli, Wang, Xiaotong, Teng, Wentao
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Under the influence of series compensation (SC) capacitance and rated voltage rise, when ultra high voltage (UHV) high SC line occurs inner fault, the short-circuit current through the SC line is greater and the residual voltage across the SC is higher, which cause the electromagnetic transient process excited by high amplitude current and voltage to be more serious in the event of fault occurrence and removal. The security of circuit breaker (CB) equipment is threatened, which make it need further research on the characteristics and put forward some effective solutions. In this study, the characteristics of macroscopic statistical distribution of peak value via short-circuit current of transient recovery voltage (TRV) across CB fracture during switching after short-circuit current zero crossing for UHV high SC line are put forward, and also of the microscopic characterization parameter of waveform rise rate and peak value time. It shows that the TRV switching capability of existing UHV CBs can not cover all the fault scenarios of high SC line. Solutions including comprehensive comparison of TRV optimal suppression measures and increase of the UHV CB switching expected TRV test requirements are put forward, which provide feasible technical scheme for CBs reliable switching of UHV high SC line.
ISSN:2051-3305
2051-3305
DOI:10.1049/joe.2018.8664