Dynamic thermal management of flashing spray cooling by the frequency conversion of compressor

•Dynamic thermal management of spray cooling was achieved by frequency conversion.•The superheat of 4 ℃ and 22 ℃ differentiates the flashing spray into three stages.•Increasing frequency from 10 Hz to 20 Hz can increase heat flux by 8.02%.•Increasing the frequency can shorten the time for the system...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied thermal engineering 2023-01, Vol.218, p.119322, Article 119322
Hauptverfasser: Wang, Shangming, Zhou, Zhifu, Chen, Bin, Thrassos, Panidis, Romeos, Alexandros, Giannadakis, Athanasios
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:•Dynamic thermal management of spray cooling was achieved by frequency conversion.•The superheat of 4 ℃ and 22 ℃ differentiates the flashing spray into three stages.•Increasing frequency from 10 Hz to 20 Hz can increase heat flux by 8.02%.•Increasing the frequency can shorten the time for the system to reach steady state.•The energy consumption for system at 15 Hz is 12.2% lower than that at 10 Hz. Dynamic thermal management of electronic equipment is of practical importance to adapt to the quickly changed heat load at local spot. A closed-loop experimental system was constructed to study the heat transfer mechanism and cooling performance of flashing spray cooling by R410A on a smooth flat copper surface in steady-state and varying operating conditions, especially the effect of frequency conversion of compressor. The results indicated that the superheat of 4 ℃ and 22 ℃ can be regarded as the transition points between three heat transfer stages of steady R410A flashing spray cooling: single-phase heat transfer, nucleate boiling, and transition boiling. To achieve the best cooling performance, superheat should be between 4 ℃ and 22 ℃ to keep heat transfer in stage II. The increase of compressor frequency can improve the cooling performance of spray system effectively. When the compressor frequencies are 10 Hz, 15 Hz and 20 Hz, CHF can reach 162.9, 168.3 and 175.0 W/cm2, and the maximum heat transfer coefficient is around 60.5, 80.6, and 90.4 kW/(m2·K), separately, with surface temperature below 35 ℃, 30 ℃ and 25 ℃. At the same heat flux, the power consumptions for the system to reach steady-state at 15 Hz and 20 Hz are 12.2% lower but 5.9% higher than that at 10 Hz, which provides a feasible energy-saving strategy for spray cooling system in the practical thermal management of electronic equipment.
ISSN:1359-4311
DOI:10.1016/j.applthermaleng.2022.119322