Study on heat transfer and pressure drop characteristics of internal heat exchangers in CO2 system under cooling condition
In order to study the heat transfer and pressure drop on four types of internal heat exchangers (IHXs) of a CO 2 system, the experiment and numerical analysis were performed under a cooling condition. The configuration of the IHXs was a coaxial type and a micro-channel type. Two loops on the gas coo...
Gespeichert in:
Veröffentlicht in: | Heat and mass transfer 2009-12, Vol.46 (2), p.187-196 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | In order to study the heat transfer and pressure drop on four types of internal heat exchangers (IHXs) of a CO
2
system, the experiment and numerical analysis were performed under a cooling condition. The configuration of the IHXs was a coaxial type and a micro-channel type. Two loops on the gas cooler part and the evaporator part were made, for experiment. And the section-by-section method and Hardy-Cross method were used for the numerical analysis. The capacity and pressure drop of the IHX are larger at the micro-channel type than at the coaxial type. When increasing the mass flow rate and the IHX length the capacity and pressure drop increase. The pressure drop of the evaporator loop is much larger than that of the gas cooler loop. The performance of the IHX was affected with operating condition of the gas-cooler and evaporator. The deviations between the experimental result and the numerical result are about ±20% for the micro-channel type and ±10% for the coaxial type. Thus, the new CO
2
heat transfer correlation should be developed to precisely predict a CO
2
heat transfer. |
---|---|
ISSN: | 0947-7411 1432-1181 |