Post-flashover compartment fires-application of a theoretical model

Numerical solutions of the post‐flashover fire are considered and a computer program is presented. The solutions are compared with experiment and the sensitivity of the solutions to a number of variables is discussed. It is shown that increasing the ventilation may either increase or decrease fire i...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Fire and materials 1979-03, Vol.3 (1), p.1-7
Hauptverfasser: Babrauskas, Vytenis, Williamson, Robert Brady
Format: Artikel
Sprache:eng
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Numerical solutions of the post‐flashover fire are considered and a computer program is presented. The solutions are compared with experiment and the sensitivity of the solutions to a number of variables is discussed. It is shown that increasing the ventilation may either increase or decrease fire intensity, and the importasnce of the ventilation controlled phase of the fire is discussed. Application of the model to calculate the expected time‐temperature history is illustrated and its significance is discussed. The deterministic approach is compared with a new method for calculating the most severe fire by letting one variable take any value between certain limits. The latter method is called pessimization. The significance for designers is noted.
ISSN:0308-0501
1099-1018
DOI:10.1002/fam.810030102