Investigation of heat pipe heat exchanger effectiveness and energy saving in air conditioning systems using silver nanofluid
The present study attempts to use the methanol-silver nanofluid filled heat pipe heat exchanger and compares the effectiveness as well as the energy saving with pure methanol. A heat pipe heat exchanger has been tested in a test rig under steady-state conditions. The lengths of both the evaporator a...
Gespeichert in:
Veröffentlicht in: | International journal of environmental science and technology (Tehran) 2013-09, Vol.9 (4) |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | The present study attempts to use the methanol-silver nanofluid
filled heat pipe heat exchanger and compares the effectiveness as well
as the energy saving with pure methanol. A heat pipe heat exchanger has
been tested in a test rig under steady-state conditions. The lengths of
both the evaporator and the condenser sections of the heat exchanger
were 700 mm, and its central adiabatic section had a length of 160 mm.
The heat exchanger had 36 plate finned copper thermosyphons arranged in
three rows. The inlet air temperature across the evaporator section was
varied in the range of 33-43 °C while the inlet air
temperature to the condenser section was nearly constant to be 13
°C. First, pure methanol was used as the working fluid with a fill
ratio of 50 % of the evaporator section length, and then dilute
dispersion of silver nanoparticles in methanol was employed as the
working fluid. The nanofluid used in the present study is 20 nm
diameter silver nanoparticles. The experiments were performed to
compare the heat pipe heat exchanger effectiveness and energy saving,
using nanofluid and pure methanol. The inlet air relative humidity
across the evaporator section was varied between 35 and 80 %. The
sensible effectiveness of the heat pipe heat exchanger obtained from
experiments varied about 5-22 % for pure methanol and 9-32
% for methanol-silver nanofluid. Based on these experimental
results, using methanol-silver nanofluid leads to energy saving
around 8.8-31.5 % for cooling and 18-100 % for reheating
the supply air stream in an air conditioning system. |
---|---|
ISSN: | 1735-1472 |