Experimental Tests of DC SFCL under Low Impedance and High Impedance Fault Conditions
DC system protection is more challenging than that for AC system due to the rapid rate of rise of the fault current and absence of natural current zero-crossing in DC systems. Superconducting fault current limiter (SFCL) in DC systems is a promising technology to reduce the fault current level and t...
Gespeichert in:
Veröffentlicht in: | IEEE Transactions on Applied Superconductivity 2021-08, Vol.31 (5), p.1-1, Article 9376895 |
---|---|
Hauptverfasser: | , , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | DC system protection is more challenging than that for AC system due to the rapid rate of rise of the fault current and absence of natural current zero-crossing in DC systems. Superconducting fault current limiter (SFCL) in DC systems is a promising technology to reduce the fault current level and the rate of rise of the fault current, and also SFCLs have no resistance during normal operation. In this paper, the behaviors of an SFCL coil are investigated under both low impedance and high impedance fault conditions in DC systems. In the low impedance fault condition system, the SFCL coil performs effective limitation of the fault current level under different prospective fault current levels. The application of SFCLs with limited inductance in the DC system can be a potential solution to effectively suppress the fault current under low impedance short-circuit faults. The SFCL coil under the high impedance fault condition can only limit the prospective fault current when it is much higher than the critical current of the coil. |
---|---|
ISSN: | 1051-8223 1558-2515 |
DOI: | 10.1109/TASC.2021.3065886 |