Assessing the Potential for Building Sector Retrofits to Mitigate ERCOT Electricity Shortfalls During Winter Storm Uri
This analysis investigates energy performance of the residential and commercial building sectors in the Electric Reliability Council of Texas (ERCOT) during Winter Storm Uri. ERCOT electricity demand was modeled for the ERCOT baseline building stock as well as for the baseline building stock retrofi...
Gespeichert in:
Hauptverfasser: | , , |
---|---|
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This analysis investigates energy performance of the residential and
commercial building sectors in the Electric Reliability Council of Texas
(ERCOT) during Winter Storm Uri. ERCOT electricity demand was modeled for the
ERCOT baseline building stock as well as for the baseline building stock
retrofitted with an efficiency upgrade package, an electrification upgrade
package, and an efficiency + electrification upgrade package. The
electrification scenario that retrofitted buildings with air-source heat pumps
(ASHPs) would have lowered ERCOT daily peak electricity demand relative to the
baseline scenario for every day of the year, except during the week of Winter
Storm Uri. As the mean outdoor temperature dropped below -5{\deg}C (23{\deg}F),
diminishing ASHP efficiency would have resulted in electrification scenario
demand exceeding the two distinct baseline scenario daily demand peaks on
February 15th and 16th (87.3 GW and 88.7 GW) to hit 111.8 GW and 117.5 GW. The
efficiency package would have lowered daily peak demand on these days to 67.0
GW and 68.0 GW. The efficiency + electrification package would have lowered
peak demand on these days to 81.5 GW and 85.6 GW. When electricity shortfall
profiles were produced by comparing modeled electricity demand to actual ERCOT
electricity generation during the storm, the results indicate that the
electrification scenario electricity shortfall (1741 GWh) would have been
larger than for the baseline scenario (1225 GWh) and the electricity shortfalls
for the efficiency scenario (347 GWh) and efficiency + electrification scenario
(704 GWh) would have been lower than the baseline. The efficiency,
electrification, and efficiency + electrification scenarios would all have
lowered summer daily peak demand due to improvements in building cooling
efficiency and would have lowered annual electricity consumption by 5.9%, 6.8%,
and 11.9%, respectively. |
---|---|
DOI: | 10.48550/arxiv.2403.01027 |