Hierarchical Control of Grid-Connected Hydrogen Electrolyzer Providing Grid Services
This paper presents the operation modes and control architecture of the grid-connected hydrogen electrolyzer systems for the provision of frequency and voltage supports. The analysis is focused on the primary and secondary loops in the hierarchical control scheme. At the power converter inner contro...
Gespeichert in:
Hauptverfasser: | , , , , |
---|---|
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This paper presents the operation modes and control architecture of the
grid-connected hydrogen electrolyzer systems for the provision of frequency and
voltage supports. The analysis is focused on the primary and secondary loops in
the hierarchical control scheme. At the power converter inner control loop, the
voltage- and current-control modes are analyzed. At the primary level, the
droop and opposite droop control strategies to provide voltage and frequency
support are described. Coordination between primary control and secondary,
tertiary reserves is discussed. The case studies and real-time simulation
results are provided using Typhoon HIL to back the theoretical investigation. |
---|---|
DOI: | 10.48550/arxiv.2211.02928 |