Smith & Wesson: The Story of a Chilled-Water Retrofit
Figure 6 shows average hourly cooling load, chilled-water flow rate, and temperature differential in the secondary chilled-water loop at various DB outdoor-air temperatures on weekdays during the cooling season. Cooling load varied from about 50 to 405 tons, following a change in DB outdoor-air temp...
Gespeichert in:
Veröffentlicht in: | Heating/Piping/Air Conditioning Engineering : HPAC 2005-07, Vol.77 (7), p.24 |
---|---|
Hauptverfasser: | , , |
Format: | Magazinearticle |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | Figure 6 shows average hourly cooling load, chilled-water flow rate, and temperature differential in the secondary chilled-water loop at various DB outdoor-air temperatures on weekdays during the cooling season. Cooling load varied from about 50 to 405 tons, following a change in DB outdoor-air temperature from 57 to 95 F. Chilled-water flow rate in the secondary loop changed from 180 to 700 gpm, while chilled-water temperature differential in the secondary loop varied from about 5 to 11 E |
---|---|