Bed-integrated local exhaust ventilation system combined with local air cleaning for improved IAQ in hospital patient rooms
The performance of a ventilated mattress (VM) used as a bed-integrated local exhaust ventilation system combined with air cleaning fabric (acid-treated activated carbon fibre (ACF) fabric) was developed and studied. The separate and combined effect of the VM and the local air cleaning for reducing t...
Gespeichert in:
Veröffentlicht in: | Building and environment 2016-05, Vol.100, p.10-18 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
container_end_page | 18 |
---|---|
container_issue | |
container_start_page | 10 |
container_title | Building and environment |
container_volume | 100 |
creator | Bivolarova, Mariya P. Melikov, Arsen K. Mizutani, Chiyomi Kajiwara, Kanji Bolashikov, Zhecho D. |
description | The performance of a ventilated mattress (VM) used as a bed-integrated local exhaust ventilation system combined with air cleaning fabric (acid-treated activated carbon fibre (ACF) fabric) was developed and studied. The separate and combined effect of the VM and the local air cleaning for reducing the exposure to body generated bio-effluents in a hospital room was determined. Full-scale experiments were conducted in a climate chamber furnished as a single-bed patient room. Two heated dummies were used to simulate a patient and a doctor in the room. The patient was lying on a bed equipped with the VM. The patient's body was covered with either a cotton sheet or with the ACF material used as a blanket. Ammonia gas released from the patient's groins simulated the body generated bio-effluents. At the location of the groins the surface area of the VM was perforated through which the contaminated air of the bed micro-environment was exhausted. Two modes of operation were studied: 1) the exhausted polluted air was discharged out of the room and 2) the polluted air was cleaned by the ACF material installed inside the mattress and recirculated back into the room. Both modes of operation efficiently reduced the generated bio-effluents in the room with about 70%. Reduction in the exposure to body-emitted ammonia was up to 96% when the VM was operated at only 1.5 L/s and the ACF was used as a blanket.
•Control strategies for reduction of indoor exposure to airborne body-emitted contaminants are proposed.•Exposure reduction of about 70% was achieved when the localized exhaust method was operating at airflow rate of 1.5 L/s.•The bed-integrated local exhaust combined with the local air cleaning was able to reduce the exposure to up to 96%. |
doi_str_mv | 10.1016/j.buildenv.2016.02.006 |
format | Article |
fullrecord | <record><control><sourceid>proquest_cross</sourceid><recordid>TN_cdi_proquest_miscellaneous_1805511095</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><els_id>S0360132316300439</els_id><sourcerecordid>1805511095</sourcerecordid><originalsourceid>FETCH-LOGICAL-c426t-fe3981ca6c8c4f2b1c411ce0b685f7e21e0c46a428ee1831a40d1974eb4a52c53</originalsourceid><addsrcrecordid>eNqNkVFrFDEQx4NY8Gz9CpJHX3bNJNls7s1arBYKIlTwLWSzs70cu8mZ5K6WfnlzXPusT8PAb_7MzI-Q98BaYKA-btth7-cRw6HltW8ZbxlTr8gKdC8apeWv12TFhGINCC7ekLc5b1kF10KuyNNnHBsfCt4nW3Ckc3R2pvhnY_e50AOG4mdbfAw0P-aCC3VxGXyo5IMvm2fc-kTdjDb4cE-nmKhfdikeKnRz-YP6QDcx73yp5K5m1UyaYlzyBTmb7Jzx3XM9Jz-vv9xdfWtuv3-9ubq8bZzkqjQTirUGZ5XTTk58ACcBHLJB6W7qkQMyJ5WVXCOCFmAlG2HdSxyk7bjrxDn5cMqtS_3eYy5m8dnhPNuAcZ8NaNZ1AGz9H2ivOy6hF0dUnVCXYs4JJ7NLfrHp0QAzRzFma17EmKMYw7ipYurgp9Mg1psPHpPJrj7F4egTumLG6P8V8Rf5z5yO</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype><pqid>1785241735</pqid></control><display><type>article</type><title>Bed-integrated local exhaust ventilation system combined with local air cleaning for improved IAQ in hospital patient rooms</title><source>Elsevier ScienceDirect Journals</source><creator>Bivolarova, Mariya P. ; Melikov, Arsen K. ; Mizutani, Chiyomi ; Kajiwara, Kanji ; Bolashikov, Zhecho D.</creator><creatorcontrib>Bivolarova, Mariya P. ; Melikov, Arsen K. ; Mizutani, Chiyomi ; Kajiwara, Kanji ; Bolashikov, Zhecho D.</creatorcontrib><description>The performance of a ventilated mattress (VM) used as a bed-integrated local exhaust ventilation system combined with air cleaning fabric (acid-treated activated carbon fibre (ACF) fabric) was developed and studied. The separate and combined effect of the VM and the local air cleaning for reducing the exposure to body generated bio-effluents in a hospital room was determined. Full-scale experiments were conducted in a climate chamber furnished as a single-bed patient room. Two heated dummies were used to simulate a patient and a doctor in the room. The patient was lying on a bed equipped with the VM. The patient's body was covered with either a cotton sheet or with the ACF material used as a blanket. Ammonia gas released from the patient's groins simulated the body generated bio-effluents. At the location of the groins the surface area of the VM was perforated through which the contaminated air of the bed micro-environment was exhausted. Two modes of operation were studied: 1) the exhausted polluted air was discharged out of the room and 2) the polluted air was cleaned by the ACF material installed inside the mattress and recirculated back into the room. Both modes of operation efficiently reduced the generated bio-effluents in the room with about 70%. Reduction in the exposure to body-emitted ammonia was up to 96% when the VM was operated at only 1.5 L/s and the ACF was used as a blanket.
•Control strategies for reduction of indoor exposure to airborne body-emitted contaminants are proposed.•Exposure reduction of about 70% was achieved when the localized exhaust method was operating at airflow rate of 1.5 L/s.•The bed-integrated local exhaust combined with the local air cleaning was able to reduce the exposure to up to 96%.</description><identifier>ISSN: 0360-1323</identifier><identifier>EISSN: 1873-684X</identifier><identifier>DOI: 10.1016/j.buildenv.2016.02.006</identifier><language>eng</language><publisher>Elsevier Ltd</publisher><subject>Activated carbon ; Air cleaning textiles ; Air quality ; Bed-integrated local exhaust ventilation ; Bedding ; Body-emitted pollutants ; Carbon fibers ; Cleaning ; Exhaust ; Exposure ; Fabrics ; Hospitals ; Indoor air quality ; Patients ; Simulation ; Ventilated mattress</subject><ispartof>Building and environment, 2016-05, Vol.100, p.10-18</ispartof><rights>2016 Elsevier Ltd</rights><lds50>peer_reviewed</lds50><oa>free_for_read</oa><woscitedreferencessubscribed>false</woscitedreferencessubscribed><citedby>FETCH-LOGICAL-c426t-fe3981ca6c8c4f2b1c411ce0b685f7e21e0c46a428ee1831a40d1974eb4a52c53</citedby><cites>FETCH-LOGICAL-c426t-fe3981ca6c8c4f2b1c411ce0b685f7e21e0c46a428ee1831a40d1974eb4a52c53</cites></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><linktohtml>$$Uhttps://www.sciencedirect.com/science/article/pii/S0360132316300439$$EHTML$$P50$$Gelsevier$$H</linktohtml><link.rule.ids>314,776,780,3537,27901,27902,65306</link.rule.ids></links><search><creatorcontrib>Bivolarova, Mariya P.</creatorcontrib><creatorcontrib>Melikov, Arsen K.</creatorcontrib><creatorcontrib>Mizutani, Chiyomi</creatorcontrib><creatorcontrib>Kajiwara, Kanji</creatorcontrib><creatorcontrib>Bolashikov, Zhecho D.</creatorcontrib><title>Bed-integrated local exhaust ventilation system combined with local air cleaning for improved IAQ in hospital patient rooms</title><title>Building and environment</title><description>The performance of a ventilated mattress (VM) used as a bed-integrated local exhaust ventilation system combined with air cleaning fabric (acid-treated activated carbon fibre (ACF) fabric) was developed and studied. The separate and combined effect of the VM and the local air cleaning for reducing the exposure to body generated bio-effluents in a hospital room was determined. Full-scale experiments were conducted in a climate chamber furnished as a single-bed patient room. Two heated dummies were used to simulate a patient and a doctor in the room. The patient was lying on a bed equipped with the VM. The patient's body was covered with either a cotton sheet or with the ACF material used as a blanket. Ammonia gas released from the patient's groins simulated the body generated bio-effluents. At the location of the groins the surface area of the VM was perforated through which the contaminated air of the bed micro-environment was exhausted. Two modes of operation were studied: 1) the exhausted polluted air was discharged out of the room and 2) the polluted air was cleaned by the ACF material installed inside the mattress and recirculated back into the room. Both modes of operation efficiently reduced the generated bio-effluents in the room with about 70%. Reduction in the exposure to body-emitted ammonia was up to 96% when the VM was operated at only 1.5 L/s and the ACF was used as a blanket.
•Control strategies for reduction of indoor exposure to airborne body-emitted contaminants are proposed.•Exposure reduction of about 70% was achieved when the localized exhaust method was operating at airflow rate of 1.5 L/s.•The bed-integrated local exhaust combined with the local air cleaning was able to reduce the exposure to up to 96%.</description><subject>Activated carbon</subject><subject>Air cleaning textiles</subject><subject>Air quality</subject><subject>Bed-integrated local exhaust ventilation</subject><subject>Bedding</subject><subject>Body-emitted pollutants</subject><subject>Carbon fibers</subject><subject>Cleaning</subject><subject>Exhaust</subject><subject>Exposure</subject><subject>Fabrics</subject><subject>Hospitals</subject><subject>Indoor air quality</subject><subject>Patients</subject><subject>Simulation</subject><subject>Ventilated mattress</subject><issn>0360-1323</issn><issn>1873-684X</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2016</creationdate><recordtype>article</recordtype><recordid>eNqNkVFrFDEQx4NY8Gz9CpJHX3bNJNls7s1arBYKIlTwLWSzs70cu8mZ5K6WfnlzXPusT8PAb_7MzI-Q98BaYKA-btth7-cRw6HltW8ZbxlTr8gKdC8apeWv12TFhGINCC7ekLc5b1kF10KuyNNnHBsfCt4nW3Ckc3R2pvhnY_e50AOG4mdbfAw0P-aCC3VxGXyo5IMvm2fc-kTdjDb4cE-nmKhfdikeKnRz-YP6QDcx73yp5K5m1UyaYlzyBTmb7Jzx3XM9Jz-vv9xdfWtuv3-9ubq8bZzkqjQTirUGZ5XTTk58ACcBHLJB6W7qkQMyJ5WVXCOCFmAlG2HdSxyk7bjrxDn5cMqtS_3eYy5m8dnhPNuAcZ8NaNZ1AGz9H2ivOy6hF0dUnVCXYs4JJ7NLfrHp0QAzRzFma17EmKMYw7ipYurgp9Mg1psPHpPJrj7F4egTumLG6P8V8Rf5z5yO</recordid><startdate>20160501</startdate><enddate>20160501</enddate><creator>Bivolarova, Mariya P.</creator><creator>Melikov, Arsen K.</creator><creator>Mizutani, Chiyomi</creator><creator>Kajiwara, Kanji</creator><creator>Bolashikov, Zhecho D.</creator><general>Elsevier Ltd</general><scope>AAYXX</scope><scope>CITATION</scope><scope>7SU</scope><scope>8FD</scope><scope>C1K</scope><scope>F28</scope><scope>FR3</scope><scope>KR7</scope><scope>7TV</scope></search><sort><creationdate>20160501</creationdate><title>Bed-integrated local exhaust ventilation system combined with local air cleaning for improved IAQ in hospital patient rooms</title><author>Bivolarova, Mariya P. ; Melikov, Arsen K. ; Mizutani, Chiyomi ; Kajiwara, Kanji ; Bolashikov, Zhecho D.</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-c426t-fe3981ca6c8c4f2b1c411ce0b685f7e21e0c46a428ee1831a40d1974eb4a52c53</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2016</creationdate><topic>Activated carbon</topic><topic>Air cleaning textiles</topic><topic>Air quality</topic><topic>Bed-integrated local exhaust ventilation</topic><topic>Bedding</topic><topic>Body-emitted pollutants</topic><topic>Carbon fibers</topic><topic>Cleaning</topic><topic>Exhaust</topic><topic>Exposure</topic><topic>Fabrics</topic><topic>Hospitals</topic><topic>Indoor air quality</topic><topic>Patients</topic><topic>Simulation</topic><topic>Ventilated mattress</topic><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>Bivolarova, Mariya P.</creatorcontrib><creatorcontrib>Melikov, Arsen K.</creatorcontrib><creatorcontrib>Mizutani, Chiyomi</creatorcontrib><creatorcontrib>Kajiwara, Kanji</creatorcontrib><creatorcontrib>Bolashikov, Zhecho D.</creatorcontrib><collection>CrossRef</collection><collection>Environmental Engineering Abstracts</collection><collection>Technology Research Database</collection><collection>Environmental Sciences and Pollution Management</collection><collection>ANTE: Abstracts in New Technology & Engineering</collection><collection>Engineering Research Database</collection><collection>Civil Engineering Abstracts</collection><collection>Pollution Abstracts</collection><jtitle>Building and environment</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>Bivolarova, Mariya P.</au><au>Melikov, Arsen K.</au><au>Mizutani, Chiyomi</au><au>Kajiwara, Kanji</au><au>Bolashikov, Zhecho D.</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>Bed-integrated local exhaust ventilation system combined with local air cleaning for improved IAQ in hospital patient rooms</atitle><jtitle>Building and environment</jtitle><date>2016-05-01</date><risdate>2016</risdate><volume>100</volume><spage>10</spage><epage>18</epage><pages>10-18</pages><issn>0360-1323</issn><eissn>1873-684X</eissn><abstract>The performance of a ventilated mattress (VM) used as a bed-integrated local exhaust ventilation system combined with air cleaning fabric (acid-treated activated carbon fibre (ACF) fabric) was developed and studied. The separate and combined effect of the VM and the local air cleaning for reducing the exposure to body generated bio-effluents in a hospital room was determined. Full-scale experiments were conducted in a climate chamber furnished as a single-bed patient room. Two heated dummies were used to simulate a patient and a doctor in the room. The patient was lying on a bed equipped with the VM. The patient's body was covered with either a cotton sheet or with the ACF material used as a blanket. Ammonia gas released from the patient's groins simulated the body generated bio-effluents. At the location of the groins the surface area of the VM was perforated through which the contaminated air of the bed micro-environment was exhausted. Two modes of operation were studied: 1) the exhausted polluted air was discharged out of the room and 2) the polluted air was cleaned by the ACF material installed inside the mattress and recirculated back into the room. Both modes of operation efficiently reduced the generated bio-effluents in the room with about 70%. Reduction in the exposure to body-emitted ammonia was up to 96% when the VM was operated at only 1.5 L/s and the ACF was used as a blanket.
•Control strategies for reduction of indoor exposure to airborne body-emitted contaminants are proposed.•Exposure reduction of about 70% was achieved when the localized exhaust method was operating at airflow rate of 1.5 L/s.•The bed-integrated local exhaust combined with the local air cleaning was able to reduce the exposure to up to 96%.</abstract><pub>Elsevier Ltd</pub><doi>10.1016/j.buildenv.2016.02.006</doi><tpages>9</tpages><oa>free_for_read</oa></addata></record> |
fulltext | fulltext |
identifier | ISSN: 0360-1323 |
ispartof | Building and environment, 2016-05, Vol.100, p.10-18 |
issn | 0360-1323 1873-684X |
language | eng |
recordid | cdi_proquest_miscellaneous_1805511095 |
source | Elsevier ScienceDirect Journals |
subjects | Activated carbon Air cleaning textiles Air quality Bed-integrated local exhaust ventilation Bedding Body-emitted pollutants Carbon fibers Cleaning Exhaust Exposure Fabrics Hospitals Indoor air quality Patients Simulation Ventilated mattress |
title | Bed-integrated local exhaust ventilation system combined with local air cleaning for improved IAQ in hospital patient rooms |
url | https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-02-01T03%3A58%3A44IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-proquest_cross&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=Bed-integrated%20local%20exhaust%20ventilation%20system%20combined%20with%20local%20air%20cleaning%20for%20improved%20IAQ%20in%20hospital%20patient%20rooms&rft.jtitle=Building%20and%20environment&rft.au=Bivolarova,%20Mariya%20P.&rft.date=2016-05-01&rft.volume=100&rft.spage=10&rft.epage=18&rft.pages=10-18&rft.issn=0360-1323&rft.eissn=1873-684X&rft_id=info:doi/10.1016/j.buildenv.2016.02.006&rft_dat=%3Cproquest_cross%3E1805511095%3C/proquest_cross%3E%3Curl%3E%3C/url%3E&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_pqid=1785241735&rft_id=info:pmid/&rft_els_id=S0360132316300439&rfr_iscdi=true |