Thermodynamic Analysis of R410A Refrigeration Cycle with a Two-Phase Ejector

A thermodynamic analysis of the ejector expansion refrigeration cycle (EERC) was carried out based on a two-phase flow model. First the ejector parameter was optimized under the given condition. Then the influence of condenser temperature and evaporator was investigated. Numerical simulation result...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied Mechanics and Materials 2014-06, Vol.590 (Innovative Solutions in the Field of Engineering Sciences), p.110-115
Hauptverfasser: Liang, Yuan Yuan, Chen, Jiang Ping, Hu, Ji Chao
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:A thermodynamic analysis of the ejector expansion refrigeration cycle (EERC) was carried out based on a two-phase flow model. First the ejector parameter was optimized under the given condition. Then the influence of condenser temperature and evaporator was investigated. Numerical simulation result shows that the EERC always has a better performance than the basic system. When the evaporator is 0°C, the system COP can be improved by 18.6%.
ISSN:1660-9336
1662-7482
1662-7482
DOI:10.4028/www.scientific.net/AMM.590.110