Unbalanced phase-to-phase voltage compensators applied to radial distribution feeders

This paper describes an application of a thyristor-controlled reactive power compensator (TCRC), which aims at individually controlling phase-to-phase voltage imbalancing in radial distribution feeders. The compensator model is straightforward included into the classical three-phase load flow formul...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on power delivery 2004-04, Vol.19 (2), p.806-812
1. Verfasser: Pires, R.C.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper describes an application of a thyristor-controlled reactive power compensator (TCRC), which aims at individually controlling phase-to-phase voltage imbalancing in radial distribution feeders. The compensator model is straightforward included into the classical three-phase load flow formulation. The Newton-Raphson iterative solution is obtained through an algorithm based on the orthogonal Givens rotation. The solution method allows to overcome the usual ill-conditioned Jacobian matrix problem arised from radial networks with high R/X ratios. Large amount of simulations are carried out in order to evaluate the TCRC model robustness.