Ground-Fault Feeder Detection With Fault-Current and Fault-Resistance Measurement in Mine Power Systems

Many mine power systems operate with a floating neutral or are high-resistance grounded, and earth fault current is no more than a few tens of amperes. Traditional earth-fault-detection methods based on zero-sequence current have poor sensitivity in this case. For improvement, a fault-detection sche...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on industry applications 2008-03, Vol.44 (2), p.424-429
Hauptverfasser: Xiangjun Zeng, Li, K.K., Chan, W.L., Sheng Su, Yuanyuan Wang
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Many mine power systems operate with a floating neutral or are high-resistance grounded, and earth fault current is no more than a few tens of amperes. Traditional earth-fault-detection methods based on zero-sequence current have poor sensitivity in this case. For improvement, a fault-detection scheme with fault-current and fault-resistance measurement is presented in this paper, which is capable of detecting high-impedance ground faults. The scheme has been verified by electromagnetic-transient-program simulation, and a fault-detection prototype has been developed and tested in the laboratory. Results show that the scheme has high sensitivity and robustness.
ISSN:0093-9994
1939-9367
DOI:10.1109/TIA.2008.916744