Harmonic characteristics of HVDC transmission system and its suppression method system

In this paper, firstly, the generation of characteristic harmonics and non-characteristic harmonics, the content of each harmonic and its amplitude varying with the frequency of HVDC converter are analyzed theoretically, then, the harm of harmonics to HVDC transmission lines is introduced, and some...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Journal of physics. Conference series 2022-12, Vol.2401 (1), p.12045
Hauptverfasser: Yunfeng, Zheng, Xiaobin, Li, Haoyu, Huang
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
container_end_page
container_issue 1
container_start_page 12045
container_title Journal of physics. Conference series
container_volume 2401
creator Yunfeng, Zheng
Xiaobin, Li
Haoyu, Huang
description In this paper, firstly, the generation of characteristic harmonics and non-characteristic harmonics, the content of each harmonic and its amplitude varying with the frequency of HVDC converter are analyzed theoretically, then, the harm of harmonics to HVDC transmission lines is introduced, and some restraining measures are put forward, such as increasing converter pulsation number, installing and improving AC filter to suppress the generation of specific frequency harmonics and reduce their amplitude, so as to increase the stability of the system. Secondly, through simulation based on PSCAD/EMTDC, it is verified that 6K±1 harmonics (where K is odd) can be eliminated by increasing the converter from 6 to 12 pulsations, so as to reduce the harmonic content of transmission lines. Finally, a simulation model is built to verify that the harmonic amplitude of 12K±1 (K is a positive integer) is greatly reduced when the hybrid tuning filter is installed at 12 pulsations.
doi_str_mv 10.1088/1742-6596/2401/1/012045
format Article
fullrecord <record><control><sourceid>proquest_iop_j</sourceid><recordid>TN_cdi_proquest_journals_2756193948</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><sourcerecordid>2756193948</sourcerecordid><originalsourceid>FETCH-LOGICAL-c225t-7a080a7ab2825091dcf44e7f960e83829f5bf25ddc6fc4a67cc73ea60241375f3</originalsourceid><addsrcrecordid>eNqFkFtLwzAUgIMoOKe_wYBvwmySJk36KPUyZaCg7jVkacIybFOT7GH_3paOiSB4Xs6B850LHwCXGN1gJESGOSWzgpVFRijCGc4QJoiyIzA5dI4PtRCn4CzGDUJ5H3wClnMVGt86DfVaBaWTCS4mpyP0Fs6XdxVMQbWxcTE638K4i8k0ULU1dCnCuO26YMZWY9La13viHJxY9RnNxT5PwcfD_Xs1ny1eHp-q28VME8LSjCskkOJqRQRhqMS1tpQabssCGZELUlq2soTVtS6spqrgWvPcqAIRinPObD4FV-PeLvivrYlJbvw2tP1JSTgrcJmXVPQUHykdfIzBWNkF16iwkxjJQaIc9MhBlRwkSixHif3k9TjpfPez-vm1evsNyq4ensn_gP878Q1xNoIW</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype><pqid>2756193948</pqid></control><display><type>article</type><title>Harmonic characteristics of HVDC transmission system and its suppression method system</title><source>IOP Publishing Free Content</source><source>EZB-FREE-00999 freely available EZB journals</source><source>IOPscience extra</source><source>Alma/SFX Local Collection</source><source>Free Full-Text Journals in Chemistry</source><creator>Yunfeng, Zheng ; Xiaobin, Li ; Haoyu, Huang</creator><creatorcontrib>Yunfeng, Zheng ; Xiaobin, Li ; Haoyu, Huang</creatorcontrib><description>In this paper, firstly, the generation of characteristic harmonics and non-characteristic harmonics, the content of each harmonic and its amplitude varying with the frequency of HVDC converter are analyzed theoretically, then, the harm of harmonics to HVDC transmission lines is introduced, and some restraining measures are put forward, such as increasing converter pulsation number, installing and improving AC filter to suppress the generation of specific frequency harmonics and reduce their amplitude, so as to increase the stability of the system. Secondly, through simulation based on PSCAD/EMTDC, it is verified that 6K±1 harmonics (where K is odd) can be eliminated by increasing the converter from 6 to 12 pulsations, so as to reduce the harmonic content of transmission lines. Finally, a simulation model is built to verify that the harmonic amplitude of 12K±1 (K is a positive integer) is greatly reduced when the hybrid tuning filter is installed at 12 pulsations.</description><identifier>ISSN: 1742-6588</identifier><identifier>EISSN: 1742-6596</identifier><identifier>DOI: 10.1088/1742-6596/2401/1/012045</identifier><language>eng</language><publisher>Bristol: IOP Publishing</publisher><subject>Amplitudes ; Harmonics ; Physics ; Simulation models ; Transmission lines</subject><ispartof>Journal of physics. Conference series, 2022-12, Vol.2401 (1), p.12045</ispartof><rights>Published under licence by IOP Publishing Ltd</rights><rights>Published under licence by IOP Publishing Ltd. This work is published under http://creativecommons.org/licenses/by/3.0/ (the “License”). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.</rights><lds50>peer_reviewed</lds50><oa>free_for_read</oa><woscitedreferencessubscribed>false</woscitedreferencessubscribed></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><linktopdf>$$Uhttps://iopscience.iop.org/article/10.1088/1742-6596/2401/1/012045/pdf$$EPDF$$P50$$Giop$$Hfree_for_read</linktopdf><link.rule.ids>314,776,780,27903,27904,38847,38869,53818,53845</link.rule.ids></links><search><creatorcontrib>Yunfeng, Zheng</creatorcontrib><creatorcontrib>Xiaobin, Li</creatorcontrib><creatorcontrib>Haoyu, Huang</creatorcontrib><title>Harmonic characteristics of HVDC transmission system and its suppression method system</title><title>Journal of physics. Conference series</title><addtitle>J. Phys.: Conf. Ser</addtitle><description>In this paper, firstly, the generation of characteristic harmonics and non-characteristic harmonics, the content of each harmonic and its amplitude varying with the frequency of HVDC converter are analyzed theoretically, then, the harm of harmonics to HVDC transmission lines is introduced, and some restraining measures are put forward, such as increasing converter pulsation number, installing and improving AC filter to suppress the generation of specific frequency harmonics and reduce their amplitude, so as to increase the stability of the system. Secondly, through simulation based on PSCAD/EMTDC, it is verified that 6K±1 harmonics (where K is odd) can be eliminated by increasing the converter from 6 to 12 pulsations, so as to reduce the harmonic content of transmission lines. Finally, a simulation model is built to verify that the harmonic amplitude of 12K±1 (K is a positive integer) is greatly reduced when the hybrid tuning filter is installed at 12 pulsations.</description><subject>Amplitudes</subject><subject>Harmonics</subject><subject>Physics</subject><subject>Simulation models</subject><subject>Transmission lines</subject><issn>1742-6588</issn><issn>1742-6596</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2022</creationdate><recordtype>article</recordtype><sourceid>O3W</sourceid><sourceid>BENPR</sourceid><recordid>eNqFkFtLwzAUgIMoOKe_wYBvwmySJk36KPUyZaCg7jVkacIybFOT7GH_3paOiSB4Xs6B850LHwCXGN1gJESGOSWzgpVFRijCGc4QJoiyIzA5dI4PtRCn4CzGDUJ5H3wClnMVGt86DfVaBaWTCS4mpyP0Fs6XdxVMQbWxcTE638K4i8k0ULU1dCnCuO26YMZWY9La13viHJxY9RnNxT5PwcfD_Xs1ny1eHp-q28VME8LSjCskkOJqRQRhqMS1tpQabssCGZELUlq2soTVtS6spqrgWvPcqAIRinPObD4FV-PeLvivrYlJbvw2tP1JSTgrcJmXVPQUHykdfIzBWNkF16iwkxjJQaIc9MhBlRwkSixHif3k9TjpfPez-vm1evsNyq4ensn_gP878Q1xNoIW</recordid><startdate>20221201</startdate><enddate>20221201</enddate><creator>Yunfeng, Zheng</creator><creator>Xiaobin, Li</creator><creator>Haoyu, Huang</creator><general>IOP Publishing</general><scope>O3W</scope><scope>TSCCA</scope><scope>AAYXX</scope><scope>CITATION</scope><scope>8FD</scope><scope>8FE</scope><scope>8FG</scope><scope>ABUWG</scope><scope>AFKRA</scope><scope>ARAPS</scope><scope>AZQEC</scope><scope>BENPR</scope><scope>BGLVJ</scope><scope>CCPQU</scope><scope>DWQXO</scope><scope>H8D</scope><scope>HCIFZ</scope><scope>L7M</scope><scope>P5Z</scope><scope>P62</scope><scope>PIMPY</scope><scope>PQEST</scope><scope>PQQKQ</scope><scope>PQUKI</scope><scope>PRINS</scope></search><sort><creationdate>20221201</creationdate><title>Harmonic characteristics of HVDC transmission system and its suppression method system</title><author>Yunfeng, Zheng ; Xiaobin, Li ; Haoyu, Huang</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-c225t-7a080a7ab2825091dcf44e7f960e83829f5bf25ddc6fc4a67cc73ea60241375f3</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2022</creationdate><topic>Amplitudes</topic><topic>Harmonics</topic><topic>Physics</topic><topic>Simulation models</topic><topic>Transmission lines</topic><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>Yunfeng, Zheng</creatorcontrib><creatorcontrib>Xiaobin, Li</creatorcontrib><creatorcontrib>Haoyu, Huang</creatorcontrib><collection>IOP Publishing Free Content</collection><collection>IOPscience (Open Access)</collection><collection>CrossRef</collection><collection>Technology Research Database</collection><collection>ProQuest SciTech Collection</collection><collection>ProQuest Technology Collection</collection><collection>ProQuest Central (Alumni Edition)</collection><collection>ProQuest Central UK/Ireland</collection><collection>Advanced Technologies &amp; Aerospace Collection</collection><collection>ProQuest Central Essentials</collection><collection>ProQuest Central</collection><collection>Technology Collection</collection><collection>ProQuest One Community College</collection><collection>ProQuest Central Korea</collection><collection>Aerospace Database</collection><collection>SciTech Premium Collection</collection><collection>Advanced Technologies Database with Aerospace</collection><collection>Advanced Technologies &amp; Aerospace Database</collection><collection>ProQuest Advanced Technologies &amp; Aerospace Collection</collection><collection>Publicly Available Content Database</collection><collection>ProQuest One Academic Eastern Edition (DO NOT USE)</collection><collection>ProQuest One Academic</collection><collection>ProQuest One Academic UKI Edition</collection><collection>ProQuest Central China</collection><jtitle>Journal of physics. Conference series</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>Yunfeng, Zheng</au><au>Xiaobin, Li</au><au>Haoyu, Huang</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>Harmonic characteristics of HVDC transmission system and its suppression method system</atitle><jtitle>Journal of physics. Conference series</jtitle><addtitle>J. Phys.: Conf. Ser</addtitle><date>2022-12-01</date><risdate>2022</risdate><volume>2401</volume><issue>1</issue><spage>12045</spage><pages>12045-</pages><issn>1742-6588</issn><eissn>1742-6596</eissn><abstract>In this paper, firstly, the generation of characteristic harmonics and non-characteristic harmonics, the content of each harmonic and its amplitude varying with the frequency of HVDC converter are analyzed theoretically, then, the harm of harmonics to HVDC transmission lines is introduced, and some restraining measures are put forward, such as increasing converter pulsation number, installing and improving AC filter to suppress the generation of specific frequency harmonics and reduce their amplitude, so as to increase the stability of the system. Secondly, through simulation based on PSCAD/EMTDC, it is verified that 6K±1 harmonics (where K is odd) can be eliminated by increasing the converter from 6 to 12 pulsations, so as to reduce the harmonic content of transmission lines. Finally, a simulation model is built to verify that the harmonic amplitude of 12K±1 (K is a positive integer) is greatly reduced when the hybrid tuning filter is installed at 12 pulsations.</abstract><cop>Bristol</cop><pub>IOP Publishing</pub><doi>10.1088/1742-6596/2401/1/012045</doi><tpages>7</tpages><oa>free_for_read</oa></addata></record>
fulltext fulltext
identifier ISSN: 1742-6588
ispartof Journal of physics. Conference series, 2022-12, Vol.2401 (1), p.12045
issn 1742-6588
1742-6596
language eng
recordid cdi_proquest_journals_2756193948
source IOP Publishing Free Content; EZB-FREE-00999 freely available EZB journals; IOPscience extra; Alma/SFX Local Collection; Free Full-Text Journals in Chemistry
subjects Amplitudes
Harmonics
Physics
Simulation models
Transmission lines
title Harmonic characteristics of HVDC transmission system and its suppression method system
url https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-01-27T16%3A42%3A18IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-proquest_iop_j&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=Harmonic%20characteristics%20of%20HVDC%20transmission%20system%20and%20its%20suppression%20method%20system&rft.jtitle=Journal%20of%20physics.%20Conference%20series&rft.au=Yunfeng,%20Zheng&rft.date=2022-12-01&rft.volume=2401&rft.issue=1&rft.spage=12045&rft.pages=12045-&rft.issn=1742-6588&rft.eissn=1742-6596&rft_id=info:doi/10.1088/1742-6596/2401/1/012045&rft_dat=%3Cproquest_iop_j%3E2756193948%3C/proquest_iop_j%3E%3Curl%3E%3C/url%3E&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_pqid=2756193948&rft_id=info:pmid/&rfr_iscdi=true