Numerical study on indoor environment and thermal comfort in train station waiting hall with two different air-conditioning modes

With the increasing size of the waiting hall, the large-area use of transparent envelope materials makes the interior surface temperature of the envelope too high, which puts forward higher requirements for the control of environment and thermal comfort indoors. In this paper, the characteristics of...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Building simulation 2021-04, Vol.14 (2), p.337-349
Hauptverfasser: Zhuang, Biyao, Shi, Juan, Chen, Zhenqian
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
container_end_page 349
container_issue 2
container_start_page 337
container_title Building simulation
container_volume 14
creator Zhuang, Biyao
Shi, Juan
Chen, Zhenqian
description With the increasing size of the waiting hall, the large-area use of transparent envelope materials makes the interior surface temperature of the envelope too high, which puts forward higher requirements for the control of environment and thermal comfort indoors. In this paper, the characteristics of indoor temperature distribution, relative humidity distribution and thermal comfort under the all air system (AAs) and the radiant floor cooling and wall cooling combined with air supply system (RC/ASs) were investigated in the large spaces. The computational fluid dynamics (CFD) method was used, and the performance of the CFD model was validated by comparing the measured results with CFD simulation results in the AAs. The numerical results clearly showed that the temperature and relative humidity indoors could satisfy the design requirement both in the AAs and RC/ASs. The indoor air distribution in most areas under the RC/ASs was more uniform based on the indoor heat and humidity requirements under the cooling load of measured day. In the AAs, the total cooling capacity of air conditioning unit was the highest when indoor thermal comfort was the best, that meant that to achieve the best working condition, the air-conditioning system need high energy consumption. Meanwhile, the RC/ASs addressed the problem that the temperature around the seated passengers in the waiting area was relatively high in the AAs. This paper will provide reference for the air conditioning system design in the similar large spaces in the future.
doi_str_mv 10.1007/s12273-020-0732-0
format Article
fullrecord <record><control><sourceid>proquest_cross</sourceid><recordid>TN_cdi_proquest_journals_2479804199</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><sourcerecordid>2479804199</sourcerecordid><originalsourceid>FETCH-LOGICAL-c316t-7446d6eaf45e5c01375134add67cc5316383d638d2e7a27f1c82de250b4ff1c63</originalsourceid><addsrcrecordid>eNp1kMtKAzEYRgdRsGgfwF3AdTS3mcwspXiDohtdh5hLmzKT1CRj6dI3N2MLrsziTwLn-0JOVV1hdIMR4rcJE8IpRARBxCmB6KSa4a5rYMsZOz2ead1159U8pQ2aFkc1o7Pq-2UcTHRK9iDlUe9B8MB5HUIExn-5GPxgfAbSa5DXJg6FU2GwIeaCgRxlmSnL7EpuJ112fgXWsu_BzuU1yLsAtLPWxN8SF6EKXruJnsAhaJMuqzMr-2Tmx_2ien-4f1s8weXr4_PibgkVxU2G5SeNboy0rDa1QpjyGlMmtW64UnVBaEt1GZoYLgm3WLVEG1KjD2bLpaEX1fWhdxvD52hSFpswRl-eFITxrkWsaCoUPlAqhpSisWIb3SDjXmAkJtniIFsU2WKSLVDJkEMmFdavTPxr_j_0A4lsg_g</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype><pqid>2479804199</pqid></control><display><type>article</type><title>Numerical study on indoor environment and thermal comfort in train station waiting hall with two different air-conditioning modes</title><source>SpringerLink Journals - AutoHoldings</source><creator>Zhuang, Biyao ; Shi, Juan ; Chen, Zhenqian</creator><creatorcontrib>Zhuang, Biyao ; Shi, Juan ; Chen, Zhenqian</creatorcontrib><description>With the increasing size of the waiting hall, the large-area use of transparent envelope materials makes the interior surface temperature of the envelope too high, which puts forward higher requirements for the control of environment and thermal comfort indoors. In this paper, the characteristics of indoor temperature distribution, relative humidity distribution and thermal comfort under the all air system (AAs) and the radiant floor cooling and wall cooling combined with air supply system (RC/ASs) were investigated in the large spaces. The computational fluid dynamics (CFD) method was used, and the performance of the CFD model was validated by comparing the measured results with CFD simulation results in the AAs. The numerical results clearly showed that the temperature and relative humidity indoors could satisfy the design requirement both in the AAs and RC/ASs. The indoor air distribution in most areas under the RC/ASs was more uniform based on the indoor heat and humidity requirements under the cooling load of measured day. In the AAs, the total cooling capacity of air conditioning unit was the highest when indoor thermal comfort was the best, that meant that to achieve the best working condition, the air-conditioning system need high energy consumption. Meanwhile, the RC/ASs addressed the problem that the temperature around the seated passengers in the waiting area was relatively high in the AAs. This paper will provide reference for the air conditioning system design in the similar large spaces in the future.</description><identifier>ISSN: 1996-3599</identifier><identifier>EISSN: 1996-8744</identifier><identifier>DOI: 10.1007/s12273-020-0732-0</identifier><language>eng</language><publisher>Beijing: Tsinghua University Press</publisher><subject>Aerodynamics ; Air conditioning ; Air conditioning equipment ; Air supplies ; Atmospheric Protection/Air Quality Control/Air Pollution ; Building Construction and Design ; Computational fluid dynamics ; Cooling ; Cooling loads ; Energy consumption ; Engineering ; Engineering Thermodynamics ; Heat and Mass Transfer ; Humidity ; Indoor environments ; Mathematical models ; Monitoring/Environmental Analysis ; Radiant cooling ; Railway stations ; Relative humidity ; Research Article ; Systems design ; Temperature distribution ; Thermal comfort ; Waiting rooms</subject><ispartof>Building simulation, 2021-04, Vol.14 (2), p.337-349</ispartof><rights>Tsinghua University Press and Springer-Verlag GmbH Germany, part of Springer Nature 2020</rights><rights>Tsinghua University Press and Springer-Verlag GmbH Germany, part of Springer Nature 2020.</rights><lds50>peer_reviewed</lds50><woscitedreferencessubscribed>false</woscitedreferencessubscribed><citedby>FETCH-LOGICAL-c316t-7446d6eaf45e5c01375134add67cc5316383d638d2e7a27f1c82de250b4ff1c63</citedby><cites>FETCH-LOGICAL-c316t-7446d6eaf45e5c01375134add67cc5316383d638d2e7a27f1c82de250b4ff1c63</cites></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><linktopdf>$$Uhttps://link.springer.com/content/pdf/10.1007/s12273-020-0732-0$$EPDF$$P50$$Gspringer$$H</linktopdf><linktohtml>$$Uhttps://link.springer.com/10.1007/s12273-020-0732-0$$EHTML$$P50$$Gspringer$$H</linktohtml><link.rule.ids>314,780,784,27924,27925,41488,42557,51319</link.rule.ids></links><search><creatorcontrib>Zhuang, Biyao</creatorcontrib><creatorcontrib>Shi, Juan</creatorcontrib><creatorcontrib>Chen, Zhenqian</creatorcontrib><title>Numerical study on indoor environment and thermal comfort in train station waiting hall with two different air-conditioning modes</title><title>Building simulation</title><addtitle>Build. Simul</addtitle><description>With the increasing size of the waiting hall, the large-area use of transparent envelope materials makes the interior surface temperature of the envelope too high, which puts forward higher requirements for the control of environment and thermal comfort indoors. In this paper, the characteristics of indoor temperature distribution, relative humidity distribution and thermal comfort under the all air system (AAs) and the radiant floor cooling and wall cooling combined with air supply system (RC/ASs) were investigated in the large spaces. The computational fluid dynamics (CFD) method was used, and the performance of the CFD model was validated by comparing the measured results with CFD simulation results in the AAs. The numerical results clearly showed that the temperature and relative humidity indoors could satisfy the design requirement both in the AAs and RC/ASs. The indoor air distribution in most areas under the RC/ASs was more uniform based on the indoor heat and humidity requirements under the cooling load of measured day. In the AAs, the total cooling capacity of air conditioning unit was the highest when indoor thermal comfort was the best, that meant that to achieve the best working condition, the air-conditioning system need high energy consumption. Meanwhile, the RC/ASs addressed the problem that the temperature around the seated passengers in the waiting area was relatively high in the AAs. This paper will provide reference for the air conditioning system design in the similar large spaces in the future.</description><subject>Aerodynamics</subject><subject>Air conditioning</subject><subject>Air conditioning equipment</subject><subject>Air supplies</subject><subject>Atmospheric Protection/Air Quality Control/Air Pollution</subject><subject>Building Construction and Design</subject><subject>Computational fluid dynamics</subject><subject>Cooling</subject><subject>Cooling loads</subject><subject>Energy consumption</subject><subject>Engineering</subject><subject>Engineering Thermodynamics</subject><subject>Heat and Mass Transfer</subject><subject>Humidity</subject><subject>Indoor environments</subject><subject>Mathematical models</subject><subject>Monitoring/Environmental Analysis</subject><subject>Radiant cooling</subject><subject>Railway stations</subject><subject>Relative humidity</subject><subject>Research Article</subject><subject>Systems design</subject><subject>Temperature distribution</subject><subject>Thermal comfort</subject><subject>Waiting rooms</subject><issn>1996-3599</issn><issn>1996-8744</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2021</creationdate><recordtype>article</recordtype><recordid>eNp1kMtKAzEYRgdRsGgfwF3AdTS3mcwspXiDohtdh5hLmzKT1CRj6dI3N2MLrsziTwLn-0JOVV1hdIMR4rcJE8IpRARBxCmB6KSa4a5rYMsZOz2ead1159U8pQ2aFkc1o7Pq-2UcTHRK9iDlUe9B8MB5HUIExn-5GPxgfAbSa5DXJg6FU2GwIeaCgRxlmSnL7EpuJ112fgXWsu_BzuU1yLsAtLPWxN8SF6EKXruJnsAhaJMuqzMr-2Tmx_2ien-4f1s8weXr4_PibgkVxU2G5SeNboy0rDa1QpjyGlMmtW64UnVBaEt1GZoYLgm3WLVEG1KjD2bLpaEX1fWhdxvD52hSFpswRl-eFITxrkWsaCoUPlAqhpSisWIb3SDjXmAkJtniIFsU2WKSLVDJkEMmFdavTPxr_j_0A4lsg_g</recordid><startdate>20210401</startdate><enddate>20210401</enddate><creator>Zhuang, Biyao</creator><creator>Shi, Juan</creator><creator>Chen, Zhenqian</creator><general>Tsinghua University Press</general><general>Springer Nature B.V</general><scope>AAYXX</scope><scope>CITATION</scope></search><sort><creationdate>20210401</creationdate><title>Numerical study on indoor environment and thermal comfort in train station waiting hall with two different air-conditioning modes</title><author>Zhuang, Biyao ; Shi, Juan ; Chen, Zhenqian</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-c316t-7446d6eaf45e5c01375134add67cc5316383d638d2e7a27f1c82de250b4ff1c63</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2021</creationdate><topic>Aerodynamics</topic><topic>Air conditioning</topic><topic>Air conditioning equipment</topic><topic>Air supplies</topic><topic>Atmospheric Protection/Air Quality Control/Air Pollution</topic><topic>Building Construction and Design</topic><topic>Computational fluid dynamics</topic><topic>Cooling</topic><topic>Cooling loads</topic><topic>Energy consumption</topic><topic>Engineering</topic><topic>Engineering Thermodynamics</topic><topic>Heat and Mass Transfer</topic><topic>Humidity</topic><topic>Indoor environments</topic><topic>Mathematical models</topic><topic>Monitoring/Environmental Analysis</topic><topic>Radiant cooling</topic><topic>Railway stations</topic><topic>Relative humidity</topic><topic>Research Article</topic><topic>Systems design</topic><topic>Temperature distribution</topic><topic>Thermal comfort</topic><topic>Waiting rooms</topic><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>Zhuang, Biyao</creatorcontrib><creatorcontrib>Shi, Juan</creatorcontrib><creatorcontrib>Chen, Zhenqian</creatorcontrib><collection>CrossRef</collection><jtitle>Building simulation</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>Zhuang, Biyao</au><au>Shi, Juan</au><au>Chen, Zhenqian</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>Numerical study on indoor environment and thermal comfort in train station waiting hall with two different air-conditioning modes</atitle><jtitle>Building simulation</jtitle><stitle>Build. Simul</stitle><date>2021-04-01</date><risdate>2021</risdate><volume>14</volume><issue>2</issue><spage>337</spage><epage>349</epage><pages>337-349</pages><issn>1996-3599</issn><eissn>1996-8744</eissn><abstract>With the increasing size of the waiting hall, the large-area use of transparent envelope materials makes the interior surface temperature of the envelope too high, which puts forward higher requirements for the control of environment and thermal comfort indoors. In this paper, the characteristics of indoor temperature distribution, relative humidity distribution and thermal comfort under the all air system (AAs) and the radiant floor cooling and wall cooling combined with air supply system (RC/ASs) were investigated in the large spaces. The computational fluid dynamics (CFD) method was used, and the performance of the CFD model was validated by comparing the measured results with CFD simulation results in the AAs. The numerical results clearly showed that the temperature and relative humidity indoors could satisfy the design requirement both in the AAs and RC/ASs. The indoor air distribution in most areas under the RC/ASs was more uniform based on the indoor heat and humidity requirements under the cooling load of measured day. In the AAs, the total cooling capacity of air conditioning unit was the highest when indoor thermal comfort was the best, that meant that to achieve the best working condition, the air-conditioning system need high energy consumption. Meanwhile, the RC/ASs addressed the problem that the temperature around the seated passengers in the waiting area was relatively high in the AAs. This paper will provide reference for the air conditioning system design in the similar large spaces in the future.</abstract><cop>Beijing</cop><pub>Tsinghua University Press</pub><doi>10.1007/s12273-020-0732-0</doi><tpages>13</tpages></addata></record>
fulltext fulltext
identifier ISSN: 1996-3599
ispartof Building simulation, 2021-04, Vol.14 (2), p.337-349
issn 1996-3599
1996-8744
language eng
recordid cdi_proquest_journals_2479804199
source SpringerLink Journals - AutoHoldings
subjects Aerodynamics
Air conditioning
Air conditioning equipment
Air supplies
Atmospheric Protection/Air Quality Control/Air Pollution
Building Construction and Design
Computational fluid dynamics
Cooling
Cooling loads
Energy consumption
Engineering
Engineering Thermodynamics
Heat and Mass Transfer
Humidity
Indoor environments
Mathematical models
Monitoring/Environmental Analysis
Radiant cooling
Railway stations
Relative humidity
Research Article
Systems design
Temperature distribution
Thermal comfort
Waiting rooms
title Numerical study on indoor environment and thermal comfort in train station waiting hall with two different air-conditioning modes
url https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-01-06T11%3A05%3A20IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-proquest_cross&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=Numerical%20study%20on%20indoor%20environment%20and%20thermal%20comfort%20in%20train%20station%20waiting%20hall%20with%20two%20different%20air-conditioning%20modes&rft.jtitle=Building%20simulation&rft.au=Zhuang,%20Biyao&rft.date=2021-04-01&rft.volume=14&rft.issue=2&rft.spage=337&rft.epage=349&rft.pages=337-349&rft.issn=1996-3599&rft.eissn=1996-8744&rft_id=info:doi/10.1007/s12273-020-0732-0&rft_dat=%3Cproquest_cross%3E2479804199%3C/proquest_cross%3E%3Curl%3E%3C/url%3E&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_pqid=2479804199&rft_id=info:pmid/&rfr_iscdi=true