Investigation of Ferroresonance Causing Sustained High Voltage at a De-Energized 138 kV Bus: A Case Study

Ferroresonance causes overvoltage and excessive current flow on potential transformers (PT), which can cause substantial damage to PTs and interrupt the power system normal operation. In this article, a sustained overvoltage event on a de-energized 138 kV bus after the circuit breakers were opened t...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on industry applications 2019-11, Vol.55 (6), p.5675-5686
Hauptverfasser: Wang, Yunfei, Liang, Xiaodong, Pordanjani, Iraj Rahimi, Cui, Ryan, Jafari, Ali, Clark, Colin
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
container_end_page 5686
container_issue 6
container_start_page 5675
container_title IEEE transactions on industry applications
container_volume 55
creator Wang, Yunfei
Liang, Xiaodong
Pordanjani, Iraj Rahimi
Cui, Ryan
Jafari, Ali
Clark, Colin
description Ferroresonance causes overvoltage and excessive current flow on potential transformers (PT), which can cause substantial damage to PTs and interrupt the power system normal operation. In this article, a sustained overvoltage event on a de-energized 138 kV bus after the circuit breakers were opened to clear a phase A to ground fault at a Canadian transmission utility power grid is investigated. The power systems computer aided design (PSCAD) simulation model is created and validated using the field measurement data. The PSCAD simulation results indicate that the ferroresonance due to a limb-type open-core magnetic PT interacting with the grading capacitors of circuit breakers is the root cause of the problem. Due to the linearized magnetizing characteristic, the limb-type open-core PT is generally believed to be immune from ferroresonance; however, the event and simulation in this article demonstrate that the ferroresonance can still occur using this type of PT. The mitigation methods for the ferroresonance in this system are proposed; case and sensitivity studies using these methods are conducted to validate their effectiveness. In this article, the criterion on how to properly size a damping resistor or a damping reactor at the PT secondary is proposed, and the performance comparison using a damping resistor or a damping reactor for this system is demonstrated through case and sensitivity studies.
doi_str_mv 10.1109/TIA.2019.2936185
format Article
fullrecord <record><control><sourceid>proquest_RIE</sourceid><recordid>TN_cdi_proquest_journals_2314388211</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><ieee_id>8805403</ieee_id><sourcerecordid>2314388211</sourcerecordid><originalsourceid>FETCH-LOGICAL-c291t-f12249c39ff774b040ea3907d988db21eb7a76cb9967dd05058c0955b84b0bc33</originalsourceid><addsrcrecordid>eNo9kE1Lw0AQhhdRsFbvgpcFz6mzH2l2vNXa2kLBQ2uvYZNs4lbN6m4i1F_vloqnYZjnnWEeQq4ZjBgDvNssJyMODEccxZip9IQMGApMYpedkgEAigQR5Tm5CGEHwGTK5IDYZfttQmcb3VnXUlfTufHeeRNcq9vS0Knug20buu5Dp21rKrqwzSvduvdON4bqjmr6aJJZa3xjf-KYCUXftvShD_d0EuPB0HXXV_tLclbr92Cu_uqQvMxnm-kiWT0_LaeTVVJyZF1SM84llgLrOstkARKMFghZhUpVBWemyHQ2LgvEcVZVkEKqSsA0LVSEi1KIIbk97v307quPv-U71_s2nsy5YFIoxRmLFByp0rsQvKnzT28_tN_nDPKD0DwKzQ9C8z-hMXJzjFhjzD-uFKQShPgF4Tdvpw</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype><pqid>2314388211</pqid></control><display><type>article</type><title>Investigation of Ferroresonance Causing Sustained High Voltage at a De-Energized 138 kV Bus: A Case Study</title><source>IEEE Electronic Library (IEL)</source><creator>Wang, Yunfei ; Liang, Xiaodong ; Pordanjani, Iraj Rahimi ; Cui, Ryan ; Jafari, Ali ; Clark, Colin</creator><creatorcontrib>Wang, Yunfei ; Liang, Xiaodong ; Pordanjani, Iraj Rahimi ; Cui, Ryan ; Jafari, Ali ; Clark, Colin</creatorcontrib><description>Ferroresonance causes overvoltage and excessive current flow on potential transformers (PT), which can cause substantial damage to PTs and interrupt the power system normal operation. In this article, a sustained overvoltage event on a de-energized 138 kV bus after the circuit breakers were opened to clear a phase A to ground fault at a Canadian transmission utility power grid is investigated. The power systems computer aided design (PSCAD) simulation model is created and validated using the field measurement data. The PSCAD simulation results indicate that the ferroresonance due to a limb-type open-core magnetic PT interacting with the grading capacitors of circuit breakers is the root cause of the problem. Due to the linearized magnetizing characteristic, the limb-type open-core PT is generally believed to be immune from ferroresonance; however, the event and simulation in this article demonstrate that the ferroresonance can still occur using this type of PT. The mitigation methods for the ferroresonance in this system are proposed; case and sensitivity studies using these methods are conducted to validate their effectiveness. In this article, the criterion on how to properly size a damping resistor or a damping reactor at the PT secondary is proposed, and the performance comparison using a damping resistor or a damping reactor for this system is demonstrated through case and sensitivity studies.</description><identifier>ISSN: 0093-9994</identifier><identifier>EISSN: 1939-9367</identifier><identifier>DOI: 10.1109/TIA.2019.2936185</identifier><identifier>CODEN: ITIACR</identifier><language>eng</language><publisher>New York: IEEE</publisher><subject>Activation ; CAD ; Capacitors ; Circuit breakers ; Computer aided design ; Computer simulation ; Damping ; de-energized bus ; Ferroresonance ; grading capacitance ; Inductors ; Overvoltage ; potential transformer (PT) ; Resistors ; RLC circuits ; Sensitivity ; Simulation</subject><ispartof>IEEE transactions on industry applications, 2019-11, Vol.55 (6), p.5675-5686</ispartof><rights>Copyright The Institute of Electrical and Electronics Engineers, Inc. (IEEE) 2019</rights><lds50>peer_reviewed</lds50><woscitedreferencessubscribed>false</woscitedreferencessubscribed><citedby>FETCH-LOGICAL-c291t-f12249c39ff774b040ea3907d988db21eb7a76cb9967dd05058c0955b84b0bc33</citedby><cites>FETCH-LOGICAL-c291t-f12249c39ff774b040ea3907d988db21eb7a76cb9967dd05058c0955b84b0bc33</cites><orcidid>0000-0001-9046-2150 ; 0000-0002-8089-5419</orcidid></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><linktohtml>$$Uhttps://ieeexplore.ieee.org/document/8805403$$EHTML$$P50$$Gieee$$H</linktohtml><link.rule.ids>314,776,780,792,27901,27902,54733</link.rule.ids><linktorsrc>$$Uhttps://ieeexplore.ieee.org/document/8805403$$EView_record_in_IEEE$$FView_record_in_$$GIEEE</linktorsrc></links><search><creatorcontrib>Wang, Yunfei</creatorcontrib><creatorcontrib>Liang, Xiaodong</creatorcontrib><creatorcontrib>Pordanjani, Iraj Rahimi</creatorcontrib><creatorcontrib>Cui, Ryan</creatorcontrib><creatorcontrib>Jafari, Ali</creatorcontrib><creatorcontrib>Clark, Colin</creatorcontrib><title>Investigation of Ferroresonance Causing Sustained High Voltage at a De-Energized 138 kV Bus: A Case Study</title><title>IEEE transactions on industry applications</title><addtitle>TIA</addtitle><description>Ferroresonance causes overvoltage and excessive current flow on potential transformers (PT), which can cause substantial damage to PTs and interrupt the power system normal operation. In this article, a sustained overvoltage event on a de-energized 138 kV bus after the circuit breakers were opened to clear a phase A to ground fault at a Canadian transmission utility power grid is investigated. The power systems computer aided design (PSCAD) simulation model is created and validated using the field measurement data. The PSCAD simulation results indicate that the ferroresonance due to a limb-type open-core magnetic PT interacting with the grading capacitors of circuit breakers is the root cause of the problem. Due to the linearized magnetizing characteristic, the limb-type open-core PT is generally believed to be immune from ferroresonance; however, the event and simulation in this article demonstrate that the ferroresonance can still occur using this type of PT. The mitigation methods for the ferroresonance in this system are proposed; case and sensitivity studies using these methods are conducted to validate their effectiveness. In this article, the criterion on how to properly size a damping resistor or a damping reactor at the PT secondary is proposed, and the performance comparison using a damping resistor or a damping reactor for this system is demonstrated through case and sensitivity studies.</description><subject>Activation</subject><subject>CAD</subject><subject>Capacitors</subject><subject>Circuit breakers</subject><subject>Computer aided design</subject><subject>Computer simulation</subject><subject>Damping</subject><subject>de-energized bus</subject><subject>Ferroresonance</subject><subject>grading capacitance</subject><subject>Inductors</subject><subject>Overvoltage</subject><subject>potential transformer (PT)</subject><subject>Resistors</subject><subject>RLC circuits</subject><subject>Sensitivity</subject><subject>Simulation</subject><issn>0093-9994</issn><issn>1939-9367</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2019</creationdate><recordtype>article</recordtype><sourceid>RIE</sourceid><recordid>eNo9kE1Lw0AQhhdRsFbvgpcFz6mzH2l2vNXa2kLBQ2uvYZNs4lbN6m4i1F_vloqnYZjnnWEeQq4ZjBgDvNssJyMODEccxZip9IQMGApMYpedkgEAigQR5Tm5CGEHwGTK5IDYZfttQmcb3VnXUlfTufHeeRNcq9vS0Knug20buu5Dp21rKrqwzSvduvdON4bqjmr6aJJZa3xjf-KYCUXftvShD_d0EuPB0HXXV_tLclbr92Cu_uqQvMxnm-kiWT0_LaeTVVJyZF1SM84llgLrOstkARKMFghZhUpVBWemyHQ2LgvEcVZVkEKqSsA0LVSEi1KIIbk97v307quPv-U71_s2nsy5YFIoxRmLFByp0rsQvKnzT28_tN_nDPKD0DwKzQ9C8z-hMXJzjFhjzD-uFKQShPgF4Tdvpw</recordid><startdate>201911</startdate><enddate>201911</enddate><creator>Wang, Yunfei</creator><creator>Liang, Xiaodong</creator><creator>Pordanjani, Iraj Rahimi</creator><creator>Cui, Ryan</creator><creator>Jafari, Ali</creator><creator>Clark, Colin</creator><general>IEEE</general><general>The Institute of Electrical and Electronics Engineers, Inc. (IEEE)</general><scope>97E</scope><scope>RIA</scope><scope>RIE</scope><scope>AAYXX</scope><scope>CITATION</scope><scope>7SC</scope><scope>7SP</scope><scope>8FD</scope><scope>JQ2</scope><scope>L7M</scope><scope>L~C</scope><scope>L~D</scope><orcidid>https://orcid.org/0000-0001-9046-2150</orcidid><orcidid>https://orcid.org/0000-0002-8089-5419</orcidid></search><sort><creationdate>201911</creationdate><title>Investigation of Ferroresonance Causing Sustained High Voltage at a De-Energized 138 kV Bus: A Case Study</title><author>Wang, Yunfei ; Liang, Xiaodong ; Pordanjani, Iraj Rahimi ; Cui, Ryan ; Jafari, Ali ; Clark, Colin</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-c291t-f12249c39ff774b040ea3907d988db21eb7a76cb9967dd05058c0955b84b0bc33</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2019</creationdate><topic>Activation</topic><topic>CAD</topic><topic>Capacitors</topic><topic>Circuit breakers</topic><topic>Computer aided design</topic><topic>Computer simulation</topic><topic>Damping</topic><topic>de-energized bus</topic><topic>Ferroresonance</topic><topic>grading capacitance</topic><topic>Inductors</topic><topic>Overvoltage</topic><topic>potential transformer (PT)</topic><topic>Resistors</topic><topic>RLC circuits</topic><topic>Sensitivity</topic><topic>Simulation</topic><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>Wang, Yunfei</creatorcontrib><creatorcontrib>Liang, Xiaodong</creatorcontrib><creatorcontrib>Pordanjani, Iraj Rahimi</creatorcontrib><creatorcontrib>Cui, Ryan</creatorcontrib><creatorcontrib>Jafari, Ali</creatorcontrib><creatorcontrib>Clark, Colin</creatorcontrib><collection>IEEE All-Society Periodicals Package (ASPP) 2005-present</collection><collection>IEEE All-Society Periodicals Package (ASPP) 1998-Present</collection><collection>IEEE Electronic Library (IEL)</collection><collection>CrossRef</collection><collection>Computer and Information Systems Abstracts</collection><collection>Electronics &amp; Communications Abstracts</collection><collection>Technology Research Database</collection><collection>ProQuest Computer Science Collection</collection><collection>Advanced Technologies Database with Aerospace</collection><collection>Computer and Information Systems Abstracts – Academic</collection><collection>Computer and Information Systems Abstracts Professional</collection><jtitle>IEEE transactions on industry applications</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext_linktorsrc</fulltext></delivery><addata><au>Wang, Yunfei</au><au>Liang, Xiaodong</au><au>Pordanjani, Iraj Rahimi</au><au>Cui, Ryan</au><au>Jafari, Ali</au><au>Clark, Colin</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>Investigation of Ferroresonance Causing Sustained High Voltage at a De-Energized 138 kV Bus: A Case Study</atitle><jtitle>IEEE transactions on industry applications</jtitle><stitle>TIA</stitle><date>2019-11</date><risdate>2019</risdate><volume>55</volume><issue>6</issue><spage>5675</spage><epage>5686</epage><pages>5675-5686</pages><issn>0093-9994</issn><eissn>1939-9367</eissn><coden>ITIACR</coden><abstract>Ferroresonance causes overvoltage and excessive current flow on potential transformers (PT), which can cause substantial damage to PTs and interrupt the power system normal operation. In this article, a sustained overvoltage event on a de-energized 138 kV bus after the circuit breakers were opened to clear a phase A to ground fault at a Canadian transmission utility power grid is investigated. The power systems computer aided design (PSCAD) simulation model is created and validated using the field measurement data. The PSCAD simulation results indicate that the ferroresonance due to a limb-type open-core magnetic PT interacting with the grading capacitors of circuit breakers is the root cause of the problem. Due to the linearized magnetizing characteristic, the limb-type open-core PT is generally believed to be immune from ferroresonance; however, the event and simulation in this article demonstrate that the ferroresonance can still occur using this type of PT. The mitigation methods for the ferroresonance in this system are proposed; case and sensitivity studies using these methods are conducted to validate their effectiveness. In this article, the criterion on how to properly size a damping resistor or a damping reactor at the PT secondary is proposed, and the performance comparison using a damping resistor or a damping reactor for this system is demonstrated through case and sensitivity studies.</abstract><cop>New York</cop><pub>IEEE</pub><doi>10.1109/TIA.2019.2936185</doi><tpages>12</tpages><orcidid>https://orcid.org/0000-0001-9046-2150</orcidid><orcidid>https://orcid.org/0000-0002-8089-5419</orcidid></addata></record>
fulltext fulltext_linktorsrc
identifier ISSN: 0093-9994
ispartof IEEE transactions on industry applications, 2019-11, Vol.55 (6), p.5675-5686
issn 0093-9994
1939-9367
language eng
recordid cdi_proquest_journals_2314388211
source IEEE Electronic Library (IEL)
subjects Activation
CAD
Capacitors
Circuit breakers
Computer aided design
Computer simulation
Damping
de-energized bus
Ferroresonance
grading capacitance
Inductors
Overvoltage
potential transformer (PT)
Resistors
RLC circuits
Sensitivity
Simulation
title Investigation of Ferroresonance Causing Sustained High Voltage at a De-Energized 138 kV Bus: A Case Study
url https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-02-05T20%3A11%3A42IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-proquest_RIE&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=Investigation%20of%20Ferroresonance%20Causing%20Sustained%20High%20Voltage%20at%20a%20De-Energized%20138%20kV%20Bus:%20A%20Case%20Study&rft.jtitle=IEEE%20transactions%20on%20industry%20applications&rft.au=Wang,%20Yunfei&rft.date=2019-11&rft.volume=55&rft.issue=6&rft.spage=5675&rft.epage=5686&rft.pages=5675-5686&rft.issn=0093-9994&rft.eissn=1939-9367&rft.coden=ITIACR&rft_id=info:doi/10.1109/TIA.2019.2936185&rft_dat=%3Cproquest_RIE%3E2314388211%3C/proquest_RIE%3E%3Curl%3E%3C/url%3E&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_pqid=2314388211&rft_id=info:pmid/&rft_ieee_id=8805403&rfr_iscdi=true