Introducing innovative energy performance metrics for high-level monitoring and diagnosis of telecommunication sites

•Definition ofnovel performance indexesto detect anomalous energy absorptions in TLC sites.•High level monitoring and diagnosis procedures proven effective within Energy Intelligence (EI) protocols in TLC sites.•Clustering analysis-oriented conceivement of innovative energy metrics.•Enhancement of b...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Applied thermal engineering 2018-06, Vol.137, p.277-287
Hauptverfasser: D'Aniello, Federica, Sorrentino, Marco, Rizzo, Gianfranco, Trifirò, Alena, Bedogni, Filippo
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
container_end_page 287
container_issue
container_start_page 277
container_title Applied thermal engineering
container_volume 137
creator D'Aniello, Federica
Sorrentino, Marco
Rizzo, Gianfranco
Trifirò, Alena
Bedogni, Filippo
description •Definition ofnovel performance indexesto detect anomalous energy absorptions in TLC sites.•High level monitoring and diagnosis procedures proven effective within Energy Intelligence (EI) protocols in TLC sites.•Clustering analysis-oriented conceivement of innovative energy metrics.•Enhancement of big data-based diagnosis of TLC sensors and apparatus.•Analysis and optimization of existing hardware/thermal management strategies. This paper aims at deepening the theme of monitoring and energetic diagnosis of telecommunication (TLC) central offices, via the development and application of innovative performance parameters, whose objective is to detect the presence of anomalous energy absorption of the electronic equipment and cooling systems. Firstly, extensive energy analysis is conducted by using the heating degree days (HDD) parameter, which is already consolidated in the field of efficient thermal management of data-centers. Secondly, properly designed indicators are added to this metric: the parameter of central utilization (PUC), which allows distinguishing the multi-use (e.g. combined TLC rooms and offices) from pure central offices; the index of cluster reliability (ICR), which evaluates the stability in time of the acquired data, and the reliability index (RI). The last parameter was specifically introduced to assess if a data center exhibits an unusual energy behavior with respect to a reference energy consumption benchmark, here defined for the group the site belongs to. The innovative contribution of the paper lies in the introduction and joint use of ICR and RI parameters, which can be set up as an effective diagnostic tool for telecommunications sites. The combined verification of current ICR and RI values allows outlining four possible scenarios, differentiated on the basis of the data reliability. Particularly, immediate determination of reliable and unreliable TLC sites is enabled, while the diagnostic potential is exploited to determine whether deeper investigation of energetic consumption trajectories is required. Specifically, the joint assessment of the ICR-RI pair was successfully applied to detecting the presence of anomalous TLC and cooling energy consumption data, as well as whether these abnormalities were due to inefficient thermal management or sensor malfunctioning.
doi_str_mv 10.1016/j.applthermaleng.2018.03.061
format Article
fullrecord <record><control><sourceid>proquest_cross</sourceid><recordid>TN_cdi_proquest_journals_2073130245</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><els_id>S1359431117357794</els_id><sourcerecordid>2073130245</sourcerecordid><originalsourceid>FETCH-LOGICAL-c411t-65eadd48cc5af43e3761804950e93448b2071ad7ede3541df83e1475310434553</originalsourceid><addsrcrecordid>eNqNkE1LxDAQhoso-PkfAnptzWyStgteRFxdELzoOcRk2s3SJjVJF_bfm2W9ePM0wzDvM8xTFHdAK6BQ328rNU1D2mAY1YCurxYU2oqyitZwUlxA27BS1LQ-zT0Ty5IzgPPiMsYtpbBoG35RpLVLwZtZW9cT65zfqWR3SNBh6PdkwtD5THcayYgpWB1JHpCN7TflgDscyOidTT4c8soZYqzqnY82Et-RhANqP46zszpzvSPRJozXxVmnhog3v_Wq-Fw9fzy9lm_vL-unx7dSc4BU1gKVMbzVWqiOM2RNDS3lS0FxyThvvxa0AWUaNMgEB9O1DIE3ggHljAvBrorbI3cK_nvGmOTWz8HlkzJHGTC64Ieth-OWDj7GgJ2cgh1V2Eug8uBZbuVfz_LgWVIms-ccXx3jmD_ZWQwyaotZmLEBdZLG2_-BfgCFXpHG</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype><pqid>2073130245</pqid></control><display><type>article</type><title>Introducing innovative energy performance metrics for high-level monitoring and diagnosis of telecommunication sites</title><source>Elsevier ScienceDirect Journals</source><creator>D'Aniello, Federica ; Sorrentino, Marco ; Rizzo, Gianfranco ; Trifirò, Alena ; Bedogni, Filippo</creator><creatorcontrib>D'Aniello, Federica ; Sorrentino, Marco ; Rizzo, Gianfranco ; Trifirò, Alena ; Bedogni, Filippo</creatorcontrib><description>•Definition ofnovel performance indexesto detect anomalous energy absorptions in TLC sites.•High level monitoring and diagnosis procedures proven effective within Energy Intelligence (EI) protocols in TLC sites.•Clustering analysis-oriented conceivement of innovative energy metrics.•Enhancement of big data-based diagnosis of TLC sensors and apparatus.•Analysis and optimization of existing hardware/thermal management strategies. This paper aims at deepening the theme of monitoring and energetic diagnosis of telecommunication (TLC) central offices, via the development and application of innovative performance parameters, whose objective is to detect the presence of anomalous energy absorption of the electronic equipment and cooling systems. Firstly, extensive energy analysis is conducted by using the heating degree days (HDD) parameter, which is already consolidated in the field of efficient thermal management of data-centers. Secondly, properly designed indicators are added to this metric: the parameter of central utilization (PUC), which allows distinguishing the multi-use (e.g. combined TLC rooms and offices) from pure central offices; the index of cluster reliability (ICR), which evaluates the stability in time of the acquired data, and the reliability index (RI). The last parameter was specifically introduced to assess if a data center exhibits an unusual energy behavior with respect to a reference energy consumption benchmark, here defined for the group the site belongs to. The innovative contribution of the paper lies in the introduction and joint use of ICR and RI parameters, which can be set up as an effective diagnostic tool for telecommunications sites. The combined verification of current ICR and RI values allows outlining four possible scenarios, differentiated on the basis of the data reliability. Particularly, immediate determination of reliable and unreliable TLC sites is enabled, while the diagnostic potential is exploited to determine whether deeper investigation of energetic consumption trajectories is required. Specifically, the joint assessment of the ICR-RI pair was successfully applied to detecting the presence of anomalous TLC and cooling energy consumption data, as well as whether these abnormalities were due to inefficient thermal management or sensor malfunctioning.</description><identifier>ISSN: 1359-4311</identifier><identifier>EISSN: 1873-5606</identifier><identifier>DOI: 10.1016/j.applthermaleng.2018.03.061</identifier><language>eng</language><publisher>Oxford: Elsevier Ltd</publisher><subject>Abnormalities ; Cooling systems ; Data acquisition ; Diagnostic software ; Diagnostic systems ; Electronic equipment ; Energy absorption ; Energy consumption ; Energy efficiency ; Energy intelligence ; Energy management ; Innovations ; Monitoring ; Monitoring and diagnosis ; Monitoring systems ; Offices ; Parameters ; Performance measurement ; Reliability analysis ; Stability analysis ; Telecommunication ; Telecommunications systems ; Thermal energy ; Thermal management ; Trajectory analysis</subject><ispartof>Applied thermal engineering, 2018-06, Vol.137, p.277-287</ispartof><rights>2018 Elsevier Ltd</rights><rights>Copyright Elsevier BV Jun 2018</rights><lds50>peer_reviewed</lds50><woscitedreferencessubscribed>false</woscitedreferencessubscribed><citedby>FETCH-LOGICAL-c411t-65eadd48cc5af43e3761804950e93448b2071ad7ede3541df83e1475310434553</citedby><cites>FETCH-LOGICAL-c411t-65eadd48cc5af43e3761804950e93448b2071ad7ede3541df83e1475310434553</cites><orcidid>0000-0002-9796-2657 ; 0000-0002-2167-1378</orcidid></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><linktohtml>$$Uhttps://www.sciencedirect.com/science/article/pii/S1359431117357794$$EHTML$$P50$$Gelsevier$$H</linktohtml><link.rule.ids>314,776,780,3537,27901,27902,65306</link.rule.ids></links><search><creatorcontrib>D'Aniello, Federica</creatorcontrib><creatorcontrib>Sorrentino, Marco</creatorcontrib><creatorcontrib>Rizzo, Gianfranco</creatorcontrib><creatorcontrib>Trifirò, Alena</creatorcontrib><creatorcontrib>Bedogni, Filippo</creatorcontrib><title>Introducing innovative energy performance metrics for high-level monitoring and diagnosis of telecommunication sites</title><title>Applied thermal engineering</title><description>•Definition ofnovel performance indexesto detect anomalous energy absorptions in TLC sites.•High level monitoring and diagnosis procedures proven effective within Energy Intelligence (EI) protocols in TLC sites.•Clustering analysis-oriented conceivement of innovative energy metrics.•Enhancement of big data-based diagnosis of TLC sensors and apparatus.•Analysis and optimization of existing hardware/thermal management strategies. This paper aims at deepening the theme of monitoring and energetic diagnosis of telecommunication (TLC) central offices, via the development and application of innovative performance parameters, whose objective is to detect the presence of anomalous energy absorption of the electronic equipment and cooling systems. Firstly, extensive energy analysis is conducted by using the heating degree days (HDD) parameter, which is already consolidated in the field of efficient thermal management of data-centers. Secondly, properly designed indicators are added to this metric: the parameter of central utilization (PUC), which allows distinguishing the multi-use (e.g. combined TLC rooms and offices) from pure central offices; the index of cluster reliability (ICR), which evaluates the stability in time of the acquired data, and the reliability index (RI). The last parameter was specifically introduced to assess if a data center exhibits an unusual energy behavior with respect to a reference energy consumption benchmark, here defined for the group the site belongs to. The innovative contribution of the paper lies in the introduction and joint use of ICR and RI parameters, which can be set up as an effective diagnostic tool for telecommunications sites. The combined verification of current ICR and RI values allows outlining four possible scenarios, differentiated on the basis of the data reliability. Particularly, immediate determination of reliable and unreliable TLC sites is enabled, while the diagnostic potential is exploited to determine whether deeper investigation of energetic consumption trajectories is required. Specifically, the joint assessment of the ICR-RI pair was successfully applied to detecting the presence of anomalous TLC and cooling energy consumption data, as well as whether these abnormalities were due to inefficient thermal management or sensor malfunctioning.</description><subject>Abnormalities</subject><subject>Cooling systems</subject><subject>Data acquisition</subject><subject>Diagnostic software</subject><subject>Diagnostic systems</subject><subject>Electronic equipment</subject><subject>Energy absorption</subject><subject>Energy consumption</subject><subject>Energy efficiency</subject><subject>Energy intelligence</subject><subject>Energy management</subject><subject>Innovations</subject><subject>Monitoring</subject><subject>Monitoring and diagnosis</subject><subject>Monitoring systems</subject><subject>Offices</subject><subject>Parameters</subject><subject>Performance measurement</subject><subject>Reliability analysis</subject><subject>Stability analysis</subject><subject>Telecommunication</subject><subject>Telecommunications systems</subject><subject>Thermal energy</subject><subject>Thermal management</subject><subject>Trajectory analysis</subject><issn>1359-4311</issn><issn>1873-5606</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2018</creationdate><recordtype>article</recordtype><recordid>eNqNkE1LxDAQhoso-PkfAnptzWyStgteRFxdELzoOcRk2s3SJjVJF_bfm2W9ePM0wzDvM8xTFHdAK6BQ328rNU1D2mAY1YCurxYU2oqyitZwUlxA27BS1LQ-zT0Ty5IzgPPiMsYtpbBoG35RpLVLwZtZW9cT65zfqWR3SNBh6PdkwtD5THcayYgpWB1JHpCN7TflgDscyOidTT4c8soZYqzqnY82Et-RhANqP46zszpzvSPRJozXxVmnhog3v_Wq-Fw9fzy9lm_vL-unx7dSc4BU1gKVMbzVWqiOM2RNDS3lS0FxyThvvxa0AWUaNMgEB9O1DIE3ggHljAvBrorbI3cK_nvGmOTWz8HlkzJHGTC64Ieth-OWDj7GgJ2cgh1V2Eug8uBZbuVfz_LgWVIms-ccXx3jmD_ZWQwyaotZmLEBdZLG2_-BfgCFXpHG</recordid><startdate>20180605</startdate><enddate>20180605</enddate><creator>D'Aniello, Federica</creator><creator>Sorrentino, Marco</creator><creator>Rizzo, Gianfranco</creator><creator>Trifirò, Alena</creator><creator>Bedogni, Filippo</creator><general>Elsevier Ltd</general><general>Elsevier BV</general><scope>AAYXX</scope><scope>CITATION</scope><scope>7TB</scope><scope>8FD</scope><scope>FR3</scope><scope>KR7</scope><orcidid>https://orcid.org/0000-0002-9796-2657</orcidid><orcidid>https://orcid.org/0000-0002-2167-1378</orcidid></search><sort><creationdate>20180605</creationdate><title>Introducing innovative energy performance metrics for high-level monitoring and diagnosis of telecommunication sites</title><author>D'Aniello, Federica ; Sorrentino, Marco ; Rizzo, Gianfranco ; Trifirò, Alena ; Bedogni, Filippo</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-c411t-65eadd48cc5af43e3761804950e93448b2071ad7ede3541df83e1475310434553</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2018</creationdate><topic>Abnormalities</topic><topic>Cooling systems</topic><topic>Data acquisition</topic><topic>Diagnostic software</topic><topic>Diagnostic systems</topic><topic>Electronic equipment</topic><topic>Energy absorption</topic><topic>Energy consumption</topic><topic>Energy efficiency</topic><topic>Energy intelligence</topic><topic>Energy management</topic><topic>Innovations</topic><topic>Monitoring</topic><topic>Monitoring and diagnosis</topic><topic>Monitoring systems</topic><topic>Offices</topic><topic>Parameters</topic><topic>Performance measurement</topic><topic>Reliability analysis</topic><topic>Stability analysis</topic><topic>Telecommunication</topic><topic>Telecommunications systems</topic><topic>Thermal energy</topic><topic>Thermal management</topic><topic>Trajectory analysis</topic><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>D'Aniello, Federica</creatorcontrib><creatorcontrib>Sorrentino, Marco</creatorcontrib><creatorcontrib>Rizzo, Gianfranco</creatorcontrib><creatorcontrib>Trifirò, Alena</creatorcontrib><creatorcontrib>Bedogni, Filippo</creatorcontrib><collection>CrossRef</collection><collection>Mechanical &amp; Transportation Engineering Abstracts</collection><collection>Technology Research Database</collection><collection>Engineering Research Database</collection><collection>Civil Engineering Abstracts</collection><jtitle>Applied thermal engineering</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>D'Aniello, Federica</au><au>Sorrentino, Marco</au><au>Rizzo, Gianfranco</au><au>Trifirò, Alena</au><au>Bedogni, Filippo</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>Introducing innovative energy performance metrics for high-level monitoring and diagnosis of telecommunication sites</atitle><jtitle>Applied thermal engineering</jtitle><date>2018-06-05</date><risdate>2018</risdate><volume>137</volume><spage>277</spage><epage>287</epage><pages>277-287</pages><issn>1359-4311</issn><eissn>1873-5606</eissn><abstract>•Definition ofnovel performance indexesto detect anomalous energy absorptions in TLC sites.•High level monitoring and diagnosis procedures proven effective within Energy Intelligence (EI) protocols in TLC sites.•Clustering analysis-oriented conceivement of innovative energy metrics.•Enhancement of big data-based diagnosis of TLC sensors and apparatus.•Analysis and optimization of existing hardware/thermal management strategies. This paper aims at deepening the theme of monitoring and energetic diagnosis of telecommunication (TLC) central offices, via the development and application of innovative performance parameters, whose objective is to detect the presence of anomalous energy absorption of the electronic equipment and cooling systems. Firstly, extensive energy analysis is conducted by using the heating degree days (HDD) parameter, which is already consolidated in the field of efficient thermal management of data-centers. Secondly, properly designed indicators are added to this metric: the parameter of central utilization (PUC), which allows distinguishing the multi-use (e.g. combined TLC rooms and offices) from pure central offices; the index of cluster reliability (ICR), which evaluates the stability in time of the acquired data, and the reliability index (RI). The last parameter was specifically introduced to assess if a data center exhibits an unusual energy behavior with respect to a reference energy consumption benchmark, here defined for the group the site belongs to. The innovative contribution of the paper lies in the introduction and joint use of ICR and RI parameters, which can be set up as an effective diagnostic tool for telecommunications sites. The combined verification of current ICR and RI values allows outlining four possible scenarios, differentiated on the basis of the data reliability. Particularly, immediate determination of reliable and unreliable TLC sites is enabled, while the diagnostic potential is exploited to determine whether deeper investigation of energetic consumption trajectories is required. Specifically, the joint assessment of the ICR-RI pair was successfully applied to detecting the presence of anomalous TLC and cooling energy consumption data, as well as whether these abnormalities were due to inefficient thermal management or sensor malfunctioning.</abstract><cop>Oxford</cop><pub>Elsevier Ltd</pub><doi>10.1016/j.applthermaleng.2018.03.061</doi><tpages>11</tpages><orcidid>https://orcid.org/0000-0002-9796-2657</orcidid><orcidid>https://orcid.org/0000-0002-2167-1378</orcidid></addata></record>
fulltext fulltext
identifier ISSN: 1359-4311
ispartof Applied thermal engineering, 2018-06, Vol.137, p.277-287
issn 1359-4311
1873-5606
language eng
recordid cdi_proquest_journals_2073130245
source Elsevier ScienceDirect Journals
subjects Abnormalities
Cooling systems
Data acquisition
Diagnostic software
Diagnostic systems
Electronic equipment
Energy absorption
Energy consumption
Energy efficiency
Energy intelligence
Energy management
Innovations
Monitoring
Monitoring and diagnosis
Monitoring systems
Offices
Parameters
Performance measurement
Reliability analysis
Stability analysis
Telecommunication
Telecommunications systems
Thermal energy
Thermal management
Trajectory analysis
title Introducing innovative energy performance metrics for high-level monitoring and diagnosis of telecommunication sites
url https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-02-09T01%3A14%3A28IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-proquest_cross&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=Introducing%20innovative%20energy%20performance%20metrics%20for%20high-level%20monitoring%20and%20diagnosis%20of%20telecommunication%20sites&rft.jtitle=Applied%20thermal%20engineering&rft.au=D'Aniello,%20Federica&rft.date=2018-06-05&rft.volume=137&rft.spage=277&rft.epage=287&rft.pages=277-287&rft.issn=1359-4311&rft.eissn=1873-5606&rft_id=info:doi/10.1016/j.applthermaleng.2018.03.061&rft_dat=%3Cproquest_cross%3E2073130245%3C/proquest_cross%3E%3Curl%3E%3C/url%3E&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_pqid=2073130245&rft_id=info:pmid/&rft_els_id=S1359431117357794&rfr_iscdi=true