On-site measured performance of a mechanically ventilated double ETFE cushion structure in an aquatics center

•Performances of double ETFE cushion structure in an aquatics center are measured.•Impact of mechanically ventilated cavity under various solar irradiances is tested.•Cavity air temperature is reduced by 7.3–10.5 °C in summer via mechanical ventilation.•Mechanically ventilated cavity achieves a heat...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Solar energy 2018-03, Vol.162, p.289-299
Hauptverfasser: Tang, Haida, Zhang, Tao, Liu, Xiaohua, Liu, Xiaochen, Xiang, Xiangjian, Jiang, Yi
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:•Performances of double ETFE cushion structure in an aquatics center are measured.•Impact of mechanically ventilated cavity under various solar irradiances is tested.•Cavity air temperature is reduced by 7.3–10.5 °C in summer via mechanical ventilation.•Mechanically ventilated cavity achieves a heat exhaust efficiency ranging 9.62–26.98.•Indoor heat gain from envelopes reduces by 45% via mechanically ventilated cavity. An ethylene tetrafluoroethylene (ETFE) cushion structure is an attractive approach as the building façade for aesthetic and sustainability reasons. This paper focuses on the operating performance of mechanically ventilated double ETFE cushion structure and indoor thermal environment in the National Aquatics Center of China, the largest building in the world utilizing the ETFE cushion structure as its building façade. Without mechanical ventilation in the cavity, the cavity air temperature reaches as high as 46–57 °C with a solar irradiance ranging 300–800 W/m2. It results in a sensible load of 78–238 W/m2 in the large space of the aquatics center without shading devices. Air temperature in the cavity could be decreased by 7.3–10.5 °C by virtue of a mechanical ventilation with an air flow rate of 830,000 m3/h. A total heat quantity ranging 2300–5800 kW is evacuated in the cavity with a heat exhaust efficiency ranging from 9.62 to 26.98. The inner surface temperature of the building envelope is significantly decreased with the help of mechanically ventilated cavity integrated with shading devices. It contributes to a lower black globe temperature in the occupied zone and a lower indoor heat gain through longwave radiation and air convection. Furthermore, preliminary test results of natural ventilation in the double ETFE cushion structure reveal its feasibility and potential for energy conservation.
ISSN:0038-092X
1471-1257
DOI:10.1016/j.solener.2018.01.042