A Verification Test Result of Isolated Operation of a Microgrid Configured with New Energy Generators and a Study of Improvement of Voltage Control

Verification test result of isolated operation of a microgird configured with some new energy generators on Aichi EXPO. 2005 showed stable controllability without rotating machine. However, improvement of voltage fluctuation with changing reactive power of loads had been hoped. Some improvements of...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Denki Gakkai ronbunshi. B, Enerugi, denki kiki, denryoku Enerugi, denki kiki, denryoku, 2009, Vol.129 (1), p.57-65
Hauptverfasser: Sumita, Jiro, Nishioka, Kojiro, Noro, Yasuhiro, Ito, Yozo, Yabuki, Masanori, Kawakami, Noriko
Format: Artikel
Sprache:eng
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Verification test result of isolated operation of a microgird configured with some new energy generators on Aichi EXPO. 2005 showed stable controllability without rotating machine. However, improvement of voltage fluctuation with changing reactive power of loads had been hoped. Some improvements of system voltage control had been implemented on the maicrogrid moved to Central Japan Airport City. This paper presents a verification test result of the improvement of voltage fluctuation in isolated operation with PAFC output power compensation control by NaS batteries and also presents a simulation study of a further improvement of voltage control strategies of PAFC inverters.
ISSN:0385-4213
1348-8147
DOI:10.1541/ieejpes.129.57