Harmonics and reactive power from line-commutated inverters in proposed photovoltaic subdivision

This paper describes how one hundred 6.6 kW line-commutated inverters in a proposed photovoltaic subdivision will affect the 10 MVA distribution feeder to which the inverters are connected. Voltage distortion and reactive power correction were studied using a special simulation computer program. The...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE Trans. Power Appar. Syst.; (United States) 1983-09, Vol.102 (9), p.3205-3211
Hauptverfasser: DUGAN, R. C, JEWELL, W. T, ROESLER, D. J
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper describes how one hundred 6.6 kW line-commutated inverters in a proposed photovoltaic subdivision will affect the 10 MVA distribution feeder to which the inverters are connected. Voltage distortion and reactive power correction were studied using a special simulation computer program. The worst-case level of voltage total harmonic distortion is 6.2%, and by setting capacitor switching practices carefully it should be possible to keep voltage THD around 2-3%. The harmonic distortion is greatly affected by the placement of capacitors on the system.
ISSN:0018-9510
DOI:10.1109/TPAS.1983.318130