Prestriking voltages associated with motor breaker closing

Steep-fronted surges arriving at motor terminals due to breaker closing result from the prestrike voltages present across each breaker pole as an arc is established. This prestrike voltage has been shown to depend on the instantaneous 60 Hz source voltage, and transients transferred through the moto...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE transactions on energy conversion 1988-12, Vol.3 (4), p.855-863
Hauptverfasser: Dick, E.P., Gupta, B.K., Pillai, P., Narang, A., Lauber, T.S., Sharma, D.K.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!