Parametric analyses for the design of a closed-loop passive containment cooling system
A design parameter study is presented for the closed-loop type passive containment cooling system (PCCS) which is equipped with two heat exchangers: one installed at the inside of the containment and the other submerged in the water pool at the outside of the containment. A GOTHIC code model for PCC...
Gespeichert in:
Veröffentlicht in: | Nuclear engineering and technology 2021, Vol.53 (4), p.1134-1145 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | kor |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
container_end_page | 1145 |
---|---|
container_issue | 4 |
container_start_page | 1134 |
container_title | Nuclear engineering and technology |
container_volume | 53 |
creator | Bang, Jungjin Hwang, Ji-Hwan Kim, Han Gon Jerng, Dong-Wook |
description | A design parameter study is presented for the closed-loop type passive containment cooling system (PCCS) which is equipped with two heat exchangers: one installed at the inside of the containment and the other submerged in the water pool at the outside of the containment. A GOTHIC code model for PCCS performance analyses was set up and the design parameters such as the heat exchanger sizes, locations, and water pool tank volumes were analyzed to investigate the feasibility of installing this type of PCCS in PWRs like OPR-1000 being operated in Korea. We identified the size of the circulation loop and heat exchangers as major design parameters affecting the performance of PCCS. The analyses showed that the heat exchangers in the inside of the containment would be more influential on the heat removal capability of PCCS than that installed in the water pool at the outside of the containment. Hence, it was recommended to down-size the heat exchangers in the water pool to optimize PCCS without compromising its performance. Based on the parametric study, it was demonstrated that a closed-loop type PCCS could be designed sufficiently compact for installation in the available space within the containment of PWRs like OPR-1000. |
format | Article |
fullrecord | <record><control><sourceid>kisti</sourceid><recordid>TN_cdi_kisti_ndsl_JAKO202124452943579</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><sourcerecordid>JAKO202124452943579</sourcerecordid><originalsourceid>FETCH-kisti_ndsl_JAKO2021244529435793</originalsourceid><addsrcrecordid>eNqNjLsKwjAUQIMoWNR_uItjoXnRdhRRRAcdRNxKbG81mCalNwj-vQ5-gNM5w-GMWCKEVKnUxXXMEp7LItW5lFO2ILK3TAnOM13whF1OZjAdxsHWYLxxb0KCNgwQHwgNkr17CC0YqF0gbFIXQg-9-V5eCHXw0VjfoY9fD876O9CbInZzNmmNI1z8OGPL7ea83qVPS9FWviFX7VeHo8gEF0ppUSqp81L-230AuT1CBQ</addsrcrecordid><sourcetype>Open Access Repository</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype></control><display><type>article</type><title>Parametric analyses for the design of a closed-loop passive containment cooling system</title><source>DOAJ Directory of Open Access Journals</source><source>Elektronische Zeitschriftenbibliothek - Frei zugängliche E-Journals</source><source>Alma/SFX Local Collection</source><creator>Bang, Jungjin ; Hwang, Ji-Hwan ; Kim, Han Gon ; Jerng, Dong-Wook</creator><creatorcontrib>Bang, Jungjin ; Hwang, Ji-Hwan ; Kim, Han Gon ; Jerng, Dong-Wook</creatorcontrib><description>A design parameter study is presented for the closed-loop type passive containment cooling system (PCCS) which is equipped with two heat exchangers: one installed at the inside of the containment and the other submerged in the water pool at the outside of the containment. A GOTHIC code model for PCCS performance analyses was set up and the design parameters such as the heat exchanger sizes, locations, and water pool tank volumes were analyzed to investigate the feasibility of installing this type of PCCS in PWRs like OPR-1000 being operated in Korea. We identified the size of the circulation loop and heat exchangers as major design parameters affecting the performance of PCCS. The analyses showed that the heat exchangers in the inside of the containment would be more influential on the heat removal capability of PCCS than that installed in the water pool at the outside of the containment. Hence, it was recommended to down-size the heat exchangers in the water pool to optimize PCCS without compromising its performance. Based on the parametric study, it was demonstrated that a closed-loop type PCCS could be designed sufficiently compact for installation in the available space within the containment of PWRs like OPR-1000.</description><identifier>ISSN: 1738-5733</identifier><identifier>EISSN: 2234-358X</identifier><language>kor</language><ispartof>Nuclear engineering and technology, 2021, Vol.53 (4), p.1134-1145</ispartof><lds50>peer_reviewed</lds50><oa>free_for_read</oa><woscitedreferencessubscribed>false</woscitedreferencessubscribed></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><link.rule.ids>230,314,776,780,881,4010</link.rule.ids></links><search><creatorcontrib>Bang, Jungjin</creatorcontrib><creatorcontrib>Hwang, Ji-Hwan</creatorcontrib><creatorcontrib>Kim, Han Gon</creatorcontrib><creatorcontrib>Jerng, Dong-Wook</creatorcontrib><title>Parametric analyses for the design of a closed-loop passive containment cooling system</title><title>Nuclear engineering and technology</title><addtitle>Nuclear engineering and technology : an international journal of the Korean Nuclear Society</addtitle><description>A design parameter study is presented for the closed-loop type passive containment cooling system (PCCS) which is equipped with two heat exchangers: one installed at the inside of the containment and the other submerged in the water pool at the outside of the containment. A GOTHIC code model for PCCS performance analyses was set up and the design parameters such as the heat exchanger sizes, locations, and water pool tank volumes were analyzed to investigate the feasibility of installing this type of PCCS in PWRs like OPR-1000 being operated in Korea. We identified the size of the circulation loop and heat exchangers as major design parameters affecting the performance of PCCS. The analyses showed that the heat exchangers in the inside of the containment would be more influential on the heat removal capability of PCCS than that installed in the water pool at the outside of the containment. Hence, it was recommended to down-size the heat exchangers in the water pool to optimize PCCS without compromising its performance. Based on the parametric study, it was demonstrated that a closed-loop type PCCS could be designed sufficiently compact for installation in the available space within the containment of PWRs like OPR-1000.</description><issn>1738-5733</issn><issn>2234-358X</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2021</creationdate><recordtype>article</recordtype><sourceid>JDI</sourceid><recordid>eNqNjLsKwjAUQIMoWNR_uItjoXnRdhRRRAcdRNxKbG81mCalNwj-vQ5-gNM5w-GMWCKEVKnUxXXMEp7LItW5lFO2ILK3TAnOM13whF1OZjAdxsHWYLxxb0KCNgwQHwgNkr17CC0YqF0gbFIXQg-9-V5eCHXw0VjfoY9fD876O9CbInZzNmmNI1z8OGPL7ea83qVPS9FWviFX7VeHo8gEF0ppUSqp81L-230AuT1CBQ</recordid><startdate>2021</startdate><enddate>2021</enddate><creator>Bang, Jungjin</creator><creator>Hwang, Ji-Hwan</creator><creator>Kim, Han Gon</creator><creator>Jerng, Dong-Wook</creator><scope>JDI</scope></search><sort><creationdate>2021</creationdate><title>Parametric analyses for the design of a closed-loop passive containment cooling system</title><author>Bang, Jungjin ; Hwang, Ji-Hwan ; Kim, Han Gon ; Jerng, Dong-Wook</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-kisti_ndsl_JAKO2021244529435793</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>kor</language><creationdate>2021</creationdate><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>Bang, Jungjin</creatorcontrib><creatorcontrib>Hwang, Ji-Hwan</creatorcontrib><creatorcontrib>Kim, Han Gon</creatorcontrib><creatorcontrib>Jerng, Dong-Wook</creatorcontrib><collection>KoreaScience</collection><jtitle>Nuclear engineering and technology</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>Bang, Jungjin</au><au>Hwang, Ji-Hwan</au><au>Kim, Han Gon</au><au>Jerng, Dong-Wook</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>Parametric analyses for the design of a closed-loop passive containment cooling system</atitle><jtitle>Nuclear engineering and technology</jtitle><addtitle>Nuclear engineering and technology : an international journal of the Korean Nuclear Society</addtitle><date>2021</date><risdate>2021</risdate><volume>53</volume><issue>4</issue><spage>1134</spage><epage>1145</epage><pages>1134-1145</pages><issn>1738-5733</issn><eissn>2234-358X</eissn><abstract>A design parameter study is presented for the closed-loop type passive containment cooling system (PCCS) which is equipped with two heat exchangers: one installed at the inside of the containment and the other submerged in the water pool at the outside of the containment. A GOTHIC code model for PCCS performance analyses was set up and the design parameters such as the heat exchanger sizes, locations, and water pool tank volumes were analyzed to investigate the feasibility of installing this type of PCCS in PWRs like OPR-1000 being operated in Korea. We identified the size of the circulation loop and heat exchangers as major design parameters affecting the performance of PCCS. The analyses showed that the heat exchangers in the inside of the containment would be more influential on the heat removal capability of PCCS than that installed in the water pool at the outside of the containment. Hence, it was recommended to down-size the heat exchangers in the water pool to optimize PCCS without compromising its performance. Based on the parametric study, it was demonstrated that a closed-loop type PCCS could be designed sufficiently compact for installation in the available space within the containment of PWRs like OPR-1000.</abstract><oa>free_for_read</oa></addata></record> |
fulltext | fulltext |
identifier | ISSN: 1738-5733 |
ispartof | Nuclear engineering and technology, 2021, Vol.53 (4), p.1134-1145 |
issn | 1738-5733 2234-358X |
language | kor |
recordid | cdi_kisti_ndsl_JAKO202124452943579 |
source | DOAJ Directory of Open Access Journals; Elektronische Zeitschriftenbibliothek - Frei zugängliche E-Journals; Alma/SFX Local Collection |
title | Parametric analyses for the design of a closed-loop passive containment cooling system |
url | https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-02-12T21%3A20%3A58IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-kisti&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=Parametric%20analyses%20for%20the%20design%20of%20a%20closed-loop%20passive%20containment%20cooling%20system&rft.jtitle=Nuclear%20engineering%20and%20technology&rft.au=Bang,%20Jungjin&rft.date=2021&rft.volume=53&rft.issue=4&rft.spage=1134&rft.epage=1145&rft.pages=1134-1145&rft.issn=1738-5733&rft.eissn=2234-358X&rft_id=info:doi/&rft_dat=%3Ckisti%3EJAKO202124452943579%3C/kisti%3E%3Curl%3E%3C/url%3E&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_id=info:pmid/&rfr_iscdi=true |