The Alternate Arm Converter "Extended-Overlap" Mode: AC Faults
This article presents ac fault ride-through strategies for the "extended-overlap" operating mode of the alternate arm converter (AAC), which is a type of modular multilevel voltage source converter that has been proposed for HVdc transmission applications. The AAC offers several benefits o...
Gespeichert in:
Veröffentlicht in: | IEEE transactions on power electronics 2021-05, Vol.36 (5), p.5371-5388 |
---|---|
Hauptverfasser: | , , , |
Format: | Artikel |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
Zusammenfassung: | This article presents ac fault ride-through strategies for the "extended-overlap" operating mode of the alternate arm converter (AAC), which is a type of modular multilevel voltage source converter that has been proposed for HVdc transmission applications. The AAC offers several benefits over the half-bridge modular multilevel converter, such as requiring fewer submodules with a smaller capacitance and providing dc fault ride-through capability. Novel symmetrical and asymmetrical ac fault ride-through strategies are described and these strategies are experimentally validated by using a small scale prototype. |
---|---|
ISSN: | 0885-8993 1941-0107 |
DOI: | 10.1109/TPEL.2020.3026568 |