Zonal guarantee technology of indoor environment for the underground diesel generator plant, part II: Application
In this paper the ZGT (zonal guarantee technology), which has been introduced in the companion paper, is applied to the deep-buried underground engineering. Then, four novel ventilation and cooling systems for the underground diesel generator plant are presented. The optimization of the location of...
Gespeichert in:
Hauptverfasser: | , , , , |
---|---|
Format: | Tagungsbericht |
Sprache: | eng |
Schlagworte: | |
Online-Zugang: | Volltext bestellen |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
container_end_page | 226 |
---|---|
container_issue | |
container_start_page | 222 |
container_title | |
container_volume | |
creator | Xibin Ma Jinsheng Wang Baoyi Cheng Wenjie Liu Guanzhong Peng |
description | In this paper the ZGT (zonal guarantee technology), which has been introduced in the companion paper, is applied to the deep-buried underground engineering. Then, four novel ventilation and cooling systems for the underground diesel generator plant are presented. The optimization of the location of the fume exactor and exhaust duct and the speed of the supply air is done by the CFD simulation for one of the ventilation and cooling system. The results show that the ZGT could remove the residual heat and contaminant effectively. It is also advised that the form 1, in which the heated air is exhausted by both sides of the duct and the fume exactor locates on the lower right of the duct, may be the most effective one. According to the numerical experiment, the temperature and the velocity profile are controlled strictly when the speed of supply air is 0.8 m/s. |
doi_str_mv | 10.1109/POWERENG.2009.4915242 |
format | Conference Proceeding |
fullrecord | <record><control><sourceid>ieee_6IE</sourceid><recordid>TN_cdi_ieee_primary_4915242</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><ieee_id>4915242</ieee_id><sourcerecordid>4915242</sourcerecordid><originalsourceid>FETCH-LOGICAL-i90t-4023f8ce367419394932da7cf4ce300aa16f54365d242cfc05d0ab91e43f106d3</originalsourceid><addsrcrecordid>eNo1kN9KAkEYxSdKSM0niGAeoLVv_u3udCdiJkhGCEE3Mu1-qxPrzDaOgW_fQHZ1OIdzfheHkDsGY8ZAP7yu3mdvs5f5mAPosdRMcckvyEgXJZNcSs41E5dk8G8gvyJ9zpTKlGJ5jwzSrtTAGS-uyehw-AIAwcpSa9kn3x_emZZujyYYFxFpxGrnfOu3J-obal3tfaDofmzwbo8u0ib5uEN6dDWGbfBJaW3xgImCDoOJqdC1iXZPOxMiXSwe6aTrWluZaL27Ib3GtAccnXVI1k-z9fQ5W67mi-lkmVkNMZPARVNWKPJCMi201ILXpqgamTIAY1jeKClyVaczqqYCVYP51AylaBjktRiS2z-sRcRNF-zehNPm_J74BTG5YXs</addsrcrecordid><sourcetype>Publisher</sourcetype><iscdi>true</iscdi><recordtype>conference_proceeding</recordtype></control><display><type>conference_proceeding</type><title>Zonal guarantee technology of indoor environment for the underground diesel generator plant, part II: Application</title><source>IEEE Electronic Library (IEL) Conference Proceedings</source><creator>Xibin Ma ; Jinsheng Wang ; Baoyi Cheng ; Wenjie Liu ; Guanzhong Peng</creator><creatorcontrib>Xibin Ma ; Jinsheng Wang ; Baoyi Cheng ; Wenjie Liu ; Guanzhong Peng</creatorcontrib><description>In this paper the ZGT (zonal guarantee technology), which has been introduced in the companion paper, is applied to the deep-buried underground engineering. Then, four novel ventilation and cooling systems for the underground diesel generator plant are presented. The optimization of the location of the fume exactor and exhaust duct and the speed of the supply air is done by the CFD simulation for one of the ventilation and cooling system. The results show that the ZGT could remove the residual heat and contaminant effectively. It is also advised that the form 1, in which the heated air is exhausted by both sides of the duct and the fume exactor locates on the lower right of the duct, may be the most effective one. According to the numerical experiment, the temperature and the velocity profile are controlled strictly when the speed of supply air is 0.8 m/s.</description><identifier>ISSN: 2155-5516</identifier><identifier>ISBN: 1424422906</identifier><identifier>ISBN: 9781424446117</identifier><identifier>ISBN: 9781424422906</identifier><identifier>ISBN: 1424446112</identifier><identifier>EISBN: 9781424422913</identifier><identifier>EISBN: 1424422914</identifier><identifier>DOI: 10.1109/POWERENG.2009.4915242</identifier><identifier>LCCN: 2008902127</identifier><language>eng</language><publisher>IEEE</publisher><subject>Computational fluid dynamics ; Cooling ; Design engineering ; Ducts ; Filters ; Indoor environments ; Power generation ; Programmable logic arrays ; Temperature control ; Ventilation</subject><ispartof>2009 International Conference on Power Engineering, Energy and Electrical Drives, 2009, p.222-226</ispartof><woscitedreferencessubscribed>false</woscitedreferencessubscribed></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><linktohtml>$$Uhttps://ieeexplore.ieee.org/document/4915242$$EHTML$$P50$$Gieee$$H</linktohtml><link.rule.ids>309,310,780,784,789,790,2058,27925,54920</link.rule.ids><linktorsrc>$$Uhttps://ieeexplore.ieee.org/document/4915242$$EView_record_in_IEEE$$FView_record_in_$$GIEEE</linktorsrc></links><search><creatorcontrib>Xibin Ma</creatorcontrib><creatorcontrib>Jinsheng Wang</creatorcontrib><creatorcontrib>Baoyi Cheng</creatorcontrib><creatorcontrib>Wenjie Liu</creatorcontrib><creatorcontrib>Guanzhong Peng</creatorcontrib><title>Zonal guarantee technology of indoor environment for the underground diesel generator plant, part II: Application</title><title>2009 International Conference on Power Engineering, Energy and Electrical Drives</title><addtitle>POWERENG</addtitle><description>In this paper the ZGT (zonal guarantee technology), which has been introduced in the companion paper, is applied to the deep-buried underground engineering. Then, four novel ventilation and cooling systems for the underground diesel generator plant are presented. The optimization of the location of the fume exactor and exhaust duct and the speed of the supply air is done by the CFD simulation for one of the ventilation and cooling system. The results show that the ZGT could remove the residual heat and contaminant effectively. It is also advised that the form 1, in which the heated air is exhausted by both sides of the duct and the fume exactor locates on the lower right of the duct, may be the most effective one. According to the numerical experiment, the temperature and the velocity profile are controlled strictly when the speed of supply air is 0.8 m/s.</description><subject>Computational fluid dynamics</subject><subject>Cooling</subject><subject>Design engineering</subject><subject>Ducts</subject><subject>Filters</subject><subject>Indoor environments</subject><subject>Power generation</subject><subject>Programmable logic arrays</subject><subject>Temperature control</subject><subject>Ventilation</subject><issn>2155-5516</issn><isbn>1424422906</isbn><isbn>9781424446117</isbn><isbn>9781424422906</isbn><isbn>1424446112</isbn><isbn>9781424422913</isbn><isbn>1424422914</isbn><fulltext>true</fulltext><rsrctype>conference_proceeding</rsrctype><creationdate>2009</creationdate><recordtype>conference_proceeding</recordtype><sourceid>6IE</sourceid><sourceid>RIE</sourceid><recordid>eNo1kN9KAkEYxSdKSM0niGAeoLVv_u3udCdiJkhGCEE3Mu1-qxPrzDaOgW_fQHZ1OIdzfheHkDsGY8ZAP7yu3mdvs5f5mAPosdRMcckvyEgXJZNcSs41E5dk8G8gvyJ9zpTKlGJ5jwzSrtTAGS-uyehw-AIAwcpSa9kn3x_emZZujyYYFxFpxGrnfOu3J-obal3tfaDofmzwbo8u0ib5uEN6dDWGbfBJaW3xgImCDoOJqdC1iXZPOxMiXSwe6aTrWluZaL27Ib3GtAccnXVI1k-z9fQ5W67mi-lkmVkNMZPARVNWKPJCMi201ILXpqgamTIAY1jeKClyVaczqqYCVYP51AylaBjktRiS2z-sRcRNF-zehNPm_J74BTG5YXs</recordid><startdate>200903</startdate><enddate>200903</enddate><creator>Xibin Ma</creator><creator>Jinsheng Wang</creator><creator>Baoyi Cheng</creator><creator>Wenjie Liu</creator><creator>Guanzhong Peng</creator><general>IEEE</general><scope>6IE</scope><scope>6IL</scope><scope>CBEJK</scope><scope>RIE</scope><scope>RIL</scope></search><sort><creationdate>200903</creationdate><title>Zonal guarantee technology of indoor environment for the underground diesel generator plant, part II: Application</title><author>Xibin Ma ; Jinsheng Wang ; Baoyi Cheng ; Wenjie Liu ; Guanzhong Peng</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-i90t-4023f8ce367419394932da7cf4ce300aa16f54365d242cfc05d0ab91e43f106d3</frbrgroupid><rsrctype>conference_proceedings</rsrctype><prefilter>conference_proceedings</prefilter><language>eng</language><creationdate>2009</creationdate><topic>Computational fluid dynamics</topic><topic>Cooling</topic><topic>Design engineering</topic><topic>Ducts</topic><topic>Filters</topic><topic>Indoor environments</topic><topic>Power generation</topic><topic>Programmable logic arrays</topic><topic>Temperature control</topic><topic>Ventilation</topic><toplevel>online_resources</toplevel><creatorcontrib>Xibin Ma</creatorcontrib><creatorcontrib>Jinsheng Wang</creatorcontrib><creatorcontrib>Baoyi Cheng</creatorcontrib><creatorcontrib>Wenjie Liu</creatorcontrib><creatorcontrib>Guanzhong Peng</creatorcontrib><collection>IEEE Electronic Library (IEL) Conference Proceedings</collection><collection>IEEE Proceedings Order Plan All Online (POP All Online) 1998-present by volume</collection><collection>IEEE Xplore All Conference Proceedings</collection><collection>IEEE Electronic Library (IEL)</collection><collection>IEEE Proceedings Order Plans (POP All) 1998-Present</collection></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext_linktorsrc</fulltext></delivery><addata><au>Xibin Ma</au><au>Jinsheng Wang</au><au>Baoyi Cheng</au><au>Wenjie Liu</au><au>Guanzhong Peng</au><format>book</format><genre>proceeding</genre><ristype>CONF</ristype><atitle>Zonal guarantee technology of indoor environment for the underground diesel generator plant, part II: Application</atitle><btitle>2009 International Conference on Power Engineering, Energy and Electrical Drives</btitle><stitle>POWERENG</stitle><date>2009-03</date><risdate>2009</risdate><spage>222</spage><epage>226</epage><pages>222-226</pages><issn>2155-5516</issn><isbn>1424422906</isbn><isbn>9781424446117</isbn><isbn>9781424422906</isbn><isbn>1424446112</isbn><eisbn>9781424422913</eisbn><eisbn>1424422914</eisbn><abstract>In this paper the ZGT (zonal guarantee technology), which has been introduced in the companion paper, is applied to the deep-buried underground engineering. Then, four novel ventilation and cooling systems for the underground diesel generator plant are presented. The optimization of the location of the fume exactor and exhaust duct and the speed of the supply air is done by the CFD simulation for one of the ventilation and cooling system. The results show that the ZGT could remove the residual heat and contaminant effectively. It is also advised that the form 1, in which the heated air is exhausted by both sides of the duct and the fume exactor locates on the lower right of the duct, may be the most effective one. According to the numerical experiment, the temperature and the velocity profile are controlled strictly when the speed of supply air is 0.8 m/s.</abstract><pub>IEEE</pub><doi>10.1109/POWERENG.2009.4915242</doi><tpages>5</tpages></addata></record> |
fulltext | fulltext_linktorsrc |
identifier | ISSN: 2155-5516 |
ispartof | 2009 International Conference on Power Engineering, Energy and Electrical Drives, 2009, p.222-226 |
issn | 2155-5516 |
language | eng |
recordid | cdi_ieee_primary_4915242 |
source | IEEE Electronic Library (IEL) Conference Proceedings |
subjects | Computational fluid dynamics Cooling Design engineering Ducts Filters Indoor environments Power generation Programmable logic arrays Temperature control Ventilation |
title | Zonal guarantee technology of indoor environment for the underground diesel generator plant, part II: Application |
url | https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2024-12-26T19%3A58%3A59IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-ieee_6IE&rft_val_fmt=info:ofi/fmt:kev:mtx:book&rft.genre=proceeding&rft.atitle=Zonal%20guarantee%20technology%20of%20indoor%20environment%20for%20the%20underground%20diesel%20generator%20plant,%20part%20II:%20Application&rft.btitle=2009%20International%20Conference%20on%20Power%20Engineering,%20Energy%20and%20Electrical%20Drives&rft.au=Xibin%20Ma&rft.date=2009-03&rft.spage=222&rft.epage=226&rft.pages=222-226&rft.issn=2155-5516&rft.isbn=1424422906&rft.isbn_list=9781424446117&rft.isbn_list=9781424422906&rft.isbn_list=1424446112&rft_id=info:doi/10.1109/POWERENG.2009.4915242&rft_dat=%3Cieee_6IE%3E4915242%3C/ieee_6IE%3E%3Curl%3E%3C/url%3E&rft.eisbn=9781424422913&rft.eisbn_list=1424422914&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_id=info:pmid/&rft_ieee_id=4915242&rfr_iscdi=true |