Analysis of Accumulation of Inadvertent Interchange Energy and Time Error in Interconnected Power Systems

The causes of accumulation of inadvertent interchange energy are investigated using two area analysis. This analysis is based on vector decomposition and is illustrated on the two dimensional (ε,Ii) plane. Accumulation of inadvertent interchange energy Ii and the decomposed vector components caused...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:IEEE Trans. Power Syst.; (United States) 1986-05, Vol.1 (2), p.138-145
Hauptverfasser: Fouad, A. A., Kwon, S. H., Schulte, R. P.
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:The causes of accumulation of inadvertent interchange energy are investigated using two area analysis. This analysis is based on vector decomposition and is illustrated on the two dimensional (ε,Ii) plane. Accumulation of inadvertent interchange energy Ii and the decomposed vector components caused by areas i and r, (εi, Iii) and (εr, Iir), are investigated through the computer simulation of a six-area system. The selective participation in time error correction and the effect of introducing frequency offset are considered. It is shown that the present two-step correction scheme of time error and inadvertent interchange energy can be modified to reduce unnecessary regulation.
ISSN:0885-8950
1558-0679
DOI:10.1109/TPWRS.1986.4334920