Development of a new fault location algorithm for multi-terminal two parallel transmission lines

Conventional fault location methods using one-terminal AC voltage and current are not applicable to multi-terminal systems. A new fault location algorithm for multi-terminal two parallel transmission lines is described. This method uses the magnitude of the differential currents at each terminal and...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Nagasawa, T., Abe, M., Otsuzuki, N., Emura, T., Jikihara, Y., Takeuchi, M.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Conventional fault location methods using one-terminal AC voltage and current are not applicable to multi-terminal systems. A new fault location algorithm for multi-terminal two parallel transmission lines is described. This method uses the magnitude of the differential currents at each terminal and also uses an algorithm based on a 3-terminal fault location algorithm and an equivalent conversion from an n-terminal to a 3-terminal system. For a multi-fault occurring at the same place and same time on both lines as well as a single-fault this new algorithm is reasonably accurate. EMTP simulation results are shown.< >
DOI:10.1109/TDC.1991.169531