An adaptive internal model control for reactive power compensation

This paper presents an adaptive approach for reactive current extraction and adaptive shunt compensation of a three-phase system under unbalanced and time-varying frequency conditions. The reactive current component is extracted based on the concept of instantaneous symmetrical components. The extra...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Karimi-Ghartemani, M., Katiraei, F.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:This paper presents an adaptive approach for reactive current extraction and adaptive shunt compensation of a three-phase system under unbalanced and time-varying frequency conditions. The reactive current component is extracted based on the concept of instantaneous symmetrical components. The extracted signals are then utilized by a shunt, PWM, voltage-sourced converter to adaptively compensate the reactive power. The converter control is based on a closed-loop adaptive internal-model strategy which dynamically adjusts itself to the variations in the system frequency. Feasibility of the proposed method is illustrated in a distribution system and computer simulations are presented
ISSN:1085-1992
2576-3210
DOI:10.1109/CCA.2005.1507372