Commissioning and on-line testing of GIS and GIL

Partial discharge measurements are used to validate the integrity of the insulation system when commissioning gas-insulated switchgear and lines (GIS, GIL). On the other hand, an increasing population of service aged GIS equipment has reached its originally projected lifetime. On-line partial discha...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Hauptverfasser: Gross, D.W., Soller, M.
Format: Tagungsbericht
Sprache:eng
Schlagworte:
Online-Zugang:Volltext bestellen
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
Beschreibung
Zusammenfassung:Partial discharge measurements are used to validate the integrity of the insulation system when commissioning gas-insulated switchgear and lines (GIS, GIL). On the other hand, an increasing population of service aged GIS equipment has reached its originally projected lifetime. On-line partial discharge measurements utilizing acoustic as well as UHF sensors help keeping such equipment in service. External ring antennas, window sensors, or embedded sensors allow survey type measurements and monitoring of the partial discharge activity in the UHF range. Acoustic measurements offer excellent sensitivity with so-called bouncing particles. Field experience applying a compact instrument that combines the application of UHF and ultrasonic measurements is presented.
ISSN:1089-084X
DOI:10.1109/ELINSL.2004.1380554