Heterotrophic Plate Count Can Predict the Presence of ILegionella/I spp. in Cooling Towers

Legionella pneumophila (Lp) colonizes aquatic environments and is a potential pathogen to humans, causing outbreaks of Legionnaire’s disease. It is mainly associated with contaminated cooling towers (CTs). Several regulations, including Spanish legislation (Sl), have introduced the analysis of heter...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:Pathogens (Basel) 2023-03, Vol.12 (3)
Hauptverfasser: Sanchis, Marta, Inza, Isabel, Figueras, Maria José
Format: Artikel
Sprache:eng
Schlagworte:
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
container_end_page
container_issue 3
container_start_page
container_title Pathogens (Basel)
container_volume 12
creator Sanchis, Marta
Inza, Isabel
Figueras, Maria José
description Legionella pneumophila (Lp) colonizes aquatic environments and is a potential pathogen to humans, causing outbreaks of Legionnaire’s disease. It is mainly associated with contaminated cooling towers (CTs). Several regulations, including Spanish legislation (Sl), have introduced the analysis of heterotrophic plate count (HPC) bacteria and Legionella spp. (Lsp) in management plans to prevent and control Legionella outbreaks from CTs. The 2003 Sl for CTs (RD 865/2003) considered that concentrations of HPC bacteria ≤10,000 cfu/mL and of Lsp ≤100 cfu/L are safe; therefore, no action is required, whereas management actions should be implemented above these standards. We have investigated to what extent the proposed standard for HPC bacteria is useful to predict the presence of Lsp in cooling waters. For this, we analyzed Lsp and HPC concentrations, water temperature, and the levels of chlorine in 1376 water samples from 17 CTs. The results showed that in the 1138 water samples negative for Legionella spp. (LN), the HPC geometric mean was significantly lower (83 cfu/mL, p < 0.05) than in the positive Lsp. samples (135 cfu/mL). Of the 238 (17.3%) LP samples, 88.4% (210/238) were associated with values of HPC ≤10,000 cfu/mL and most of them showed HPC concentrations ≤100 (53.7%). In addition, a relatively low percentage of LP (28/238, 11.6%) samples were associated with HPC bacteria concentrations >10,000 cfu/mL, indicating that this standard does not predict the colonization risk for Legionella in the CTs studied. The present study has demonstrated that a threshold concentration ≤100 cfu/mL of HPC bacteria could better predict the higher concentration of Legionella in CTs, which will aid in preventing possible outbreaks.
doi_str_mv 10.3390/pathogens12030466
format Article
fullrecord <record><control><sourceid>gale</sourceid><recordid>TN_cdi_gale_infotracmisc_A743769558</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><galeid>A743769558</galeid><sourcerecordid>A743769558</sourcerecordid><originalsourceid>FETCH-LOGICAL-g678-4330576e99aa495f3fcfb12ac8b52b4c780be3837cb44494ccf8974257fe111a3</originalsourceid><addsrcrecordid>eNptT7FqwzAUFKWFhjQf0E3Q2YlkyZY0BtM2AUMzZOoSZOXJUXEkY6n096vQDhny3vDuHncHh9AzJUvGFFmNOp1CDz7SkjDC6_oOzUoi6oJIKu6v8CNaxPhF8khy4TP0uYEEU0hTGE_O4N2gE-AmfPuEG-3xboKjMwmnE1xwBG8AB4u3LfQueBgGvdriOI5L7Hz2hcH5Hu_DD0zxCT1YPURY_N852r-97ptN0X68b5t1W_S1kAVnjFSiBqW05qqyzBrb0VIb2VVlx42QpAMmmTAd51xxY6xUgpeVsEAp1WyOXv5iez3AwXmby2hzdtEc1oIzUauqklm1vKHKe4SzM7mJdfl_ZfgFF2RlXA</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype></control><display><type>article</type><title>Heterotrophic Plate Count Can Predict the Presence of ILegionella/I spp. in Cooling Towers</title><source>DOAJ Directory of Open Access Journals</source><source>Elektronische Zeitschriftenbibliothek - Frei zugängliche E-Journals</source><source>PubMed Central Open Access</source><source>MDPI - Multidisciplinary Digital Publishing Institute</source><source>PubMed Central</source><creator>Sanchis, Marta ; Inza, Isabel ; Figueras, Maria José</creator><creatorcontrib>Sanchis, Marta ; Inza, Isabel ; Figueras, Maria José</creatorcontrib><description>Legionella pneumophila (Lp) colonizes aquatic environments and is a potential pathogen to humans, causing outbreaks of Legionnaire’s disease. It is mainly associated with contaminated cooling towers (CTs). Several regulations, including Spanish legislation (Sl), have introduced the analysis of heterotrophic plate count (HPC) bacteria and Legionella spp. (Lsp) in management plans to prevent and control Legionella outbreaks from CTs. The 2003 Sl for CTs (RD 865/2003) considered that concentrations of HPC bacteria ≤10,000 cfu/mL and of Lsp ≤100 cfu/L are safe; therefore, no action is required, whereas management actions should be implemented above these standards. We have investigated to what extent the proposed standard for HPC bacteria is useful to predict the presence of Lsp in cooling waters. For this, we analyzed Lsp and HPC concentrations, water temperature, and the levels of chlorine in 1376 water samples from 17 CTs. The results showed that in the 1138 water samples negative for Legionella spp. (LN), the HPC geometric mean was significantly lower (83 cfu/mL, p &lt; 0.05) than in the positive Lsp. samples (135 cfu/mL). Of the 238 (17.3%) LP samples, 88.4% (210/238) were associated with values of HPC ≤10,000 cfu/mL and most of them showed HPC concentrations ≤100 (53.7%). In addition, a relatively low percentage of LP (28/238, 11.6%) samples were associated with HPC bacteria concentrations &gt;10,000 cfu/mL, indicating that this standard does not predict the colonization risk for Legionella in the CTs studied. The present study has demonstrated that a threshold concentration ≤100 cfu/mL of HPC bacteria could better predict the higher concentration of Legionella in CTs, which will aid in preventing possible outbreaks.</description><identifier>ISSN: 2076-0817</identifier><identifier>EISSN: 2076-0817</identifier><identifier>DOI: 10.3390/pathogens12030466</identifier><language>eng</language><publisher>MDPI AG</publisher><subject>Aerosols ; Care and treatment ; Contamination ; Control ; Diagnosis ; Identification and classification ; Legionella pneumophila ; Legionellosis ; Legionnaires' disease ; Risk factors</subject><ispartof>Pathogens (Basel), 2023-03, Vol.12 (3)</ispartof><rights>COPYRIGHT 2023 MDPI AG</rights><lds50>peer_reviewed</lds50><woscitedreferencessubscribed>false</woscitedreferencessubscribed></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><link.rule.ids>314,780,784,864,27922,27923</link.rule.ids></links><search><creatorcontrib>Sanchis, Marta</creatorcontrib><creatorcontrib>Inza, Isabel</creatorcontrib><creatorcontrib>Figueras, Maria José</creatorcontrib><title>Heterotrophic Plate Count Can Predict the Presence of ILegionella/I spp. in Cooling Towers</title><title>Pathogens (Basel)</title><description>Legionella pneumophila (Lp) colonizes aquatic environments and is a potential pathogen to humans, causing outbreaks of Legionnaire’s disease. It is mainly associated with contaminated cooling towers (CTs). Several regulations, including Spanish legislation (Sl), have introduced the analysis of heterotrophic plate count (HPC) bacteria and Legionella spp. (Lsp) in management plans to prevent and control Legionella outbreaks from CTs. The 2003 Sl for CTs (RD 865/2003) considered that concentrations of HPC bacteria ≤10,000 cfu/mL and of Lsp ≤100 cfu/L are safe; therefore, no action is required, whereas management actions should be implemented above these standards. We have investigated to what extent the proposed standard for HPC bacteria is useful to predict the presence of Lsp in cooling waters. For this, we analyzed Lsp and HPC concentrations, water temperature, and the levels of chlorine in 1376 water samples from 17 CTs. The results showed that in the 1138 water samples negative for Legionella spp. (LN), the HPC geometric mean was significantly lower (83 cfu/mL, p &lt; 0.05) than in the positive Lsp. samples (135 cfu/mL). Of the 238 (17.3%) LP samples, 88.4% (210/238) were associated with values of HPC ≤10,000 cfu/mL and most of them showed HPC concentrations ≤100 (53.7%). In addition, a relatively low percentage of LP (28/238, 11.6%) samples were associated with HPC bacteria concentrations &gt;10,000 cfu/mL, indicating that this standard does not predict the colonization risk for Legionella in the CTs studied. The present study has demonstrated that a threshold concentration ≤100 cfu/mL of HPC bacteria could better predict the higher concentration of Legionella in CTs, which will aid in preventing possible outbreaks.</description><subject>Aerosols</subject><subject>Care and treatment</subject><subject>Contamination</subject><subject>Control</subject><subject>Diagnosis</subject><subject>Identification and classification</subject><subject>Legionella pneumophila</subject><subject>Legionellosis</subject><subject>Legionnaires' disease</subject><subject>Risk factors</subject><issn>2076-0817</issn><issn>2076-0817</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2023</creationdate><recordtype>article</recordtype><sourceid/><recordid>eNptT7FqwzAUFKWFhjQf0E3Q2YlkyZY0BtM2AUMzZOoSZOXJUXEkY6n096vQDhny3vDuHncHh9AzJUvGFFmNOp1CDz7SkjDC6_oOzUoi6oJIKu6v8CNaxPhF8khy4TP0uYEEU0hTGE_O4N2gE-AmfPuEG-3xboKjMwmnE1xwBG8AB4u3LfQueBgGvdriOI5L7Hz2hcH5Hu_DD0zxCT1YPURY_N852r-97ptN0X68b5t1W_S1kAVnjFSiBqW05qqyzBrb0VIb2VVlx42QpAMmmTAd51xxY6xUgpeVsEAp1WyOXv5iez3AwXmby2hzdtEc1oIzUauqklm1vKHKe4SzM7mJdfl_ZfgFF2RlXA</recordid><startdate>20230301</startdate><enddate>20230301</enddate><creator>Sanchis, Marta</creator><creator>Inza, Isabel</creator><creator>Figueras, Maria José</creator><general>MDPI AG</general><scope/></search><sort><creationdate>20230301</creationdate><title>Heterotrophic Plate Count Can Predict the Presence of ILegionella/I spp. in Cooling Towers</title><author>Sanchis, Marta ; Inza, Isabel ; Figueras, Maria José</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-g678-4330576e99aa495f3fcfb12ac8b52b4c780be3837cb44494ccf8974257fe111a3</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2023</creationdate><topic>Aerosols</topic><topic>Care and treatment</topic><topic>Contamination</topic><topic>Control</topic><topic>Diagnosis</topic><topic>Identification and classification</topic><topic>Legionella pneumophila</topic><topic>Legionellosis</topic><topic>Legionnaires' disease</topic><topic>Risk factors</topic><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>Sanchis, Marta</creatorcontrib><creatorcontrib>Inza, Isabel</creatorcontrib><creatorcontrib>Figueras, Maria José</creatorcontrib><jtitle>Pathogens (Basel)</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>Sanchis, Marta</au><au>Inza, Isabel</au><au>Figueras, Maria José</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>Heterotrophic Plate Count Can Predict the Presence of ILegionella/I spp. in Cooling Towers</atitle><jtitle>Pathogens (Basel)</jtitle><date>2023-03-01</date><risdate>2023</risdate><volume>12</volume><issue>3</issue><issn>2076-0817</issn><eissn>2076-0817</eissn><abstract>Legionella pneumophila (Lp) colonizes aquatic environments and is a potential pathogen to humans, causing outbreaks of Legionnaire’s disease. It is mainly associated with contaminated cooling towers (CTs). Several regulations, including Spanish legislation (Sl), have introduced the analysis of heterotrophic plate count (HPC) bacteria and Legionella spp. (Lsp) in management plans to prevent and control Legionella outbreaks from CTs. The 2003 Sl for CTs (RD 865/2003) considered that concentrations of HPC bacteria ≤10,000 cfu/mL and of Lsp ≤100 cfu/L are safe; therefore, no action is required, whereas management actions should be implemented above these standards. We have investigated to what extent the proposed standard for HPC bacteria is useful to predict the presence of Lsp in cooling waters. For this, we analyzed Lsp and HPC concentrations, water temperature, and the levels of chlorine in 1376 water samples from 17 CTs. The results showed that in the 1138 water samples negative for Legionella spp. (LN), the HPC geometric mean was significantly lower (83 cfu/mL, p &lt; 0.05) than in the positive Lsp. samples (135 cfu/mL). Of the 238 (17.3%) LP samples, 88.4% (210/238) were associated with values of HPC ≤10,000 cfu/mL and most of them showed HPC concentrations ≤100 (53.7%). In addition, a relatively low percentage of LP (28/238, 11.6%) samples were associated with HPC bacteria concentrations &gt;10,000 cfu/mL, indicating that this standard does not predict the colonization risk for Legionella in the CTs studied. The present study has demonstrated that a threshold concentration ≤100 cfu/mL of HPC bacteria could better predict the higher concentration of Legionella in CTs, which will aid in preventing possible outbreaks.</abstract><pub>MDPI AG</pub><doi>10.3390/pathogens12030466</doi></addata></record>
fulltext fulltext
identifier ISSN: 2076-0817
ispartof Pathogens (Basel), 2023-03, Vol.12 (3)
issn 2076-0817
2076-0817
language eng
recordid cdi_gale_infotracmisc_A743769558
source DOAJ Directory of Open Access Journals; Elektronische Zeitschriftenbibliothek - Frei zugängliche E-Journals; PubMed Central Open Access; MDPI - Multidisciplinary Digital Publishing Institute; PubMed Central
subjects Aerosols
Care and treatment
Contamination
Control
Diagnosis
Identification and classification
Legionella pneumophila
Legionellosis
Legionnaires' disease
Risk factors
title Heterotrophic Plate Count Can Predict the Presence of ILegionella/I spp. in Cooling Towers
url https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-01-09T22%3A51%3A31IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-gale&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=Heterotrophic%20Plate%20Count%20Can%20Predict%20the%20Presence%20of%20ILegionella/I%20spp.%20in%20Cooling%20Towers&rft.jtitle=Pathogens%20(Basel)&rft.au=Sanchis,%20Marta&rft.date=2023-03-01&rft.volume=12&rft.issue=3&rft.issn=2076-0817&rft.eissn=2076-0817&rft_id=info:doi/10.3390/pathogens12030466&rft_dat=%3Cgale%3EA743769558%3C/gale%3E%3Curl%3E%3C/url%3E&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_id=info:pmid/&rft_galeid=A743769558&rfr_iscdi=true