A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions
The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy perform...
Gespeichert in:
Veröffentlicht in: | International journal of low carbon technologies 2021-09, Vol.16 (3), p.946-955 |
---|---|
Hauptverfasser: | , , , , |
Format: | Artikel |
Sprache: | eng |
Online-Zugang: | Volltext |
Tags: |
Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
|
container_end_page | 955 |
---|---|
container_issue | 3 |
container_start_page | 946 |
container_title | International journal of low carbon technologies |
container_volume | 16 |
creator | Lou, Siwei Huang, Yu Xia, Dawei Lun, Isaac Y F Li, Danny H W |
description | The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy performances of skylight coverage area for the air-conditioned atriums in the hot and humid regions. The energy performance with different atrium heights, glass types and the coverage ratios of the skylight are studied. The daylight performance was simulated by the ray-tracing Radiance and was transferred into EnergyPlus for energy evaluations. The finding suggested that, for hot and humid climates, the skylight coverage ratio should be controlled carefully to prevent the excessive solar heat gain. When the on/off lighting control is applied, the total energy consumption of the single-floor cases (or of the top floor for the multi-floor cases) leveled off when the coverage ratio of the skylight reached 9%. Thus, the skylight is favorable to the energy saving of the low-rise or single-floor commercial buildings only under the current assumptions, as the ground of the atrium cannot be well illuminated while the excessive solar radiation gets into the building. The skylight should be shaded in cooling seasons to prevent the excessive solar heat gains. |
doi_str_mv | 10.1093/ijlct/ctab023 |
format | Article |
fullrecord | <record><control><sourceid>oup_cross</sourceid><recordid>TN_cdi_crossref_primary_10_1093_ijlct_ctab023</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><oup_id>10.1093/ijlct/ctab023</oup_id><sourcerecordid>10.1093/ijlct/ctab023</sourcerecordid><originalsourceid>FETCH-LOGICAL-c1543-859c7d5140b2602b5c7e43c10eb19ca69105f1a718f61dedacf1bdfb90a3a7433</originalsourceid><addsrcrecordid>eNqFkD1PwzAURS0EEqUwsntkMfWL46YZqwooUiUWWIle_NG4JHFlO0j595S2AxvTu3o69w6HkHvgj8BLMXO7VqWZSljzTFyQCRT5goHI5OWffE1uYtxxLstc8An5XNKYBj1Sb2lqDI1fY-u2TaLKf5uAW0MDJuep9YGiC0z5XrvDozeaYgpu6KLrj83GJ4q9ps3QOU2D2R6geEuuLLbR3J3vlHw8P72v1mzz9vK6Wm6YApkLtpClKrSEnNfZnGe1VIXJhQJuaigVzkvg0gIWsLBz0EajslBrW5ccBRa5EFPCTrsq-BiDsdU-uA7DWAGvfuVURznVWc6Bfzjxftj_g_4ACxVpGA</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype></control><display><type>article</type><title>A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions</title><source>Oxford Journals Open Access Collection</source><source>DOAJ Directory of Open Access Journals</source><source>Elektronische Zeitschriftenbibliothek - Frei zugängliche E-Journals</source><creator>Lou, Siwei ; Huang, Yu ; Xia, Dawei ; Lun, Isaac Y F ; Li, Danny H W</creator><creatorcontrib>Lou, Siwei ; Huang, Yu ; Xia, Dawei ; Lun, Isaac Y F ; Li, Danny H W</creatorcontrib><description>The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy performances of skylight coverage area for the air-conditioned atriums in the hot and humid regions. The energy performance with different atrium heights, glass types and the coverage ratios of the skylight are studied. The daylight performance was simulated by the ray-tracing Radiance and was transferred into EnergyPlus for energy evaluations. The finding suggested that, for hot and humid climates, the skylight coverage ratio should be controlled carefully to prevent the excessive solar heat gain. When the on/off lighting control is applied, the total energy consumption of the single-floor cases (or of the top floor for the multi-floor cases) leveled off when the coverage ratio of the skylight reached 9%. Thus, the skylight is favorable to the energy saving of the low-rise or single-floor commercial buildings only under the current assumptions, as the ground of the atrium cannot be well illuminated while the excessive solar radiation gets into the building. The skylight should be shaded in cooling seasons to prevent the excessive solar heat gains.</description><identifier>ISSN: 1748-1325</identifier><identifier>EISSN: 1748-1325</identifier><identifier>DOI: 10.1093/ijlct/ctab023</identifier><language>eng</language><publisher>Oxford University Press</publisher><ispartof>International journal of low carbon technologies, 2021-09, Vol.16 (3), p.946-955</ispartof><rights>The Author(s) 2021. Published by Oxford University Press. 2021</rights><lds50>peer_reviewed</lds50><oa>free_for_read</oa><woscitedreferencessubscribed>false</woscitedreferencessubscribed><citedby>FETCH-LOGICAL-c1543-859c7d5140b2602b5c7e43c10eb19ca69105f1a718f61dedacf1bdfb90a3a7433</citedby><cites>FETCH-LOGICAL-c1543-859c7d5140b2602b5c7e43c10eb19ca69105f1a718f61dedacf1bdfb90a3a7433</cites></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><link.rule.ids>314,776,780,860,27901,27902</link.rule.ids></links><search><creatorcontrib>Lou, Siwei</creatorcontrib><creatorcontrib>Huang, Yu</creatorcontrib><creatorcontrib>Xia, Dawei</creatorcontrib><creatorcontrib>Lun, Isaac Y F</creatorcontrib><creatorcontrib>Li, Danny H W</creatorcontrib><title>A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions</title><title>International journal of low carbon technologies</title><description>The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy performances of skylight coverage area for the air-conditioned atriums in the hot and humid regions. The energy performance with different atrium heights, glass types and the coverage ratios of the skylight are studied. The daylight performance was simulated by the ray-tracing Radiance and was transferred into EnergyPlus for energy evaluations. The finding suggested that, for hot and humid climates, the skylight coverage ratio should be controlled carefully to prevent the excessive solar heat gain. When the on/off lighting control is applied, the total energy consumption of the single-floor cases (or of the top floor for the multi-floor cases) leveled off when the coverage ratio of the skylight reached 9%. Thus, the skylight is favorable to the energy saving of the low-rise or single-floor commercial buildings only under the current assumptions, as the ground of the atrium cannot be well illuminated while the excessive solar radiation gets into the building. The skylight should be shaded in cooling seasons to prevent the excessive solar heat gains.</description><issn>1748-1325</issn><issn>1748-1325</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2021</creationdate><recordtype>article</recordtype><sourceid>TOX</sourceid><recordid>eNqFkD1PwzAURS0EEqUwsntkMfWL46YZqwooUiUWWIle_NG4JHFlO0j595S2AxvTu3o69w6HkHvgj8BLMXO7VqWZSljzTFyQCRT5goHI5OWffE1uYtxxLstc8An5XNKYBj1Sb2lqDI1fY-u2TaLKf5uAW0MDJuep9YGiC0z5XrvDozeaYgpu6KLrj83GJ4q9ps3QOU2D2R6geEuuLLbR3J3vlHw8P72v1mzz9vK6Wm6YApkLtpClKrSEnNfZnGe1VIXJhQJuaigVzkvg0gIWsLBz0EajslBrW5ccBRa5EFPCTrsq-BiDsdU-uA7DWAGvfuVURznVWc6Bfzjxftj_g_4ACxVpGA</recordid><startdate>20210929</startdate><enddate>20210929</enddate><creator>Lou, Siwei</creator><creator>Huang, Yu</creator><creator>Xia, Dawei</creator><creator>Lun, Isaac Y F</creator><creator>Li, Danny H W</creator><general>Oxford University Press</general><scope>TOX</scope><scope>AAYXX</scope><scope>CITATION</scope></search><sort><creationdate>20210929</creationdate><title>A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions</title><author>Lou, Siwei ; Huang, Yu ; Xia, Dawei ; Lun, Isaac Y F ; Li, Danny H W</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-c1543-859c7d5140b2602b5c7e43c10eb19ca69105f1a718f61dedacf1bdfb90a3a7433</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2021</creationdate><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>Lou, Siwei</creatorcontrib><creatorcontrib>Huang, Yu</creatorcontrib><creatorcontrib>Xia, Dawei</creatorcontrib><creatorcontrib>Lun, Isaac Y F</creatorcontrib><creatorcontrib>Li, Danny H W</creatorcontrib><collection>Oxford Journals Open Access Collection</collection><collection>CrossRef</collection><jtitle>International journal of low carbon technologies</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>Lou, Siwei</au><au>Huang, Yu</au><au>Xia, Dawei</au><au>Lun, Isaac Y F</au><au>Li, Danny H W</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions</atitle><jtitle>International journal of low carbon technologies</jtitle><date>2021-09-29</date><risdate>2021</risdate><volume>16</volume><issue>3</issue><spage>946</spage><epage>955</epage><pages>946-955</pages><issn>1748-1325</issn><eissn>1748-1325</eissn><abstract>The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy performances of skylight coverage area for the air-conditioned atriums in the hot and humid regions. The energy performance with different atrium heights, glass types and the coverage ratios of the skylight are studied. The daylight performance was simulated by the ray-tracing Radiance and was transferred into EnergyPlus for energy evaluations. The finding suggested that, for hot and humid climates, the skylight coverage ratio should be controlled carefully to prevent the excessive solar heat gain. When the on/off lighting control is applied, the total energy consumption of the single-floor cases (or of the top floor for the multi-floor cases) leveled off when the coverage ratio of the skylight reached 9%. Thus, the skylight is favorable to the energy saving of the low-rise or single-floor commercial buildings only under the current assumptions, as the ground of the atrium cannot be well illuminated while the excessive solar radiation gets into the building. The skylight should be shaded in cooling seasons to prevent the excessive solar heat gains.</abstract><pub>Oxford University Press</pub><doi>10.1093/ijlct/ctab023</doi><tpages>10</tpages><oa>free_for_read</oa></addata></record> |
fulltext | fulltext |
identifier | ISSN: 1748-1325 |
ispartof | International journal of low carbon technologies, 2021-09, Vol.16 (3), p.946-955 |
issn | 1748-1325 1748-1325 |
language | eng |
recordid | cdi_crossref_primary_10_1093_ijlct_ctab023 |
source | Oxford Journals Open Access Collection; DOAJ Directory of Open Access Journals; Elektronische Zeitschriftenbibliothek - Frei zugängliche E-Journals |
title | A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions |
url | https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-02-09T02%3A29%3A42IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-oup_cross&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=A%20study%20of%20the%20skylight%20coverage%20ratio%20for%20air-conditioned%20atriumsin%20the%20hot%20and%20humid%20regions&rft.jtitle=International%20journal%20of%20low%20carbon%20technologies&rft.au=Lou,%20Siwei&rft.date=2021-09-29&rft.volume=16&rft.issue=3&rft.spage=946&rft.epage=955&rft.pages=946-955&rft.issn=1748-1325&rft.eissn=1748-1325&rft_id=info:doi/10.1093/ijlct/ctab023&rft_dat=%3Coup_cross%3E10.1093/ijlct/ctab023%3C/oup_cross%3E%3Curl%3E%3C/url%3E&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_id=info:pmid/&rft_oup_id=10.1093/ijlct/ctab023&rfr_iscdi=true |