A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions

The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy perform...

Ausführliche Beschreibung

Gespeichert in:
Bibliographische Detailangaben
Veröffentlicht in:International journal of low carbon technologies 2021-09, Vol.16 (3), p.946-955
Hauptverfasser: Lou, Siwei, Huang, Yu, Xia, Dawei, Lun, Isaac Y F, Li, Danny H W
Format: Artikel
Sprache:eng
Online-Zugang:Volltext
Tags: Tag hinzufügen
Keine Tags, Fügen Sie den ersten Tag hinzu!
container_end_page 955
container_issue 3
container_start_page 946
container_title International journal of low carbon technologies
container_volume 16
creator Lou, Siwei
Huang, Yu
Xia, Dawei
Lun, Isaac Y F
Li, Danny H W
description The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy performances of skylight coverage area for the air-conditioned atriums in the hot and humid regions. The energy performance with different atrium heights, glass types and the coverage ratios of the skylight are studied. The daylight performance was simulated by the ray-tracing Radiance and was transferred into EnergyPlus for energy evaluations. The finding suggested that, for hot and humid climates, the skylight coverage ratio should be controlled carefully to prevent the excessive solar heat gain. When the on/off lighting control is applied, the total energy consumption of the single-floor cases (or of the top floor for the multi-floor cases) leveled off when the coverage ratio of the skylight reached 9%. Thus, the skylight is favorable to the energy saving of the low-rise or single-floor commercial buildings only under the current assumptions, as the ground of the atrium cannot be well illuminated while the excessive solar radiation gets into the building. The skylight should be shaded in cooling seasons to prevent the excessive solar heat gains.
doi_str_mv 10.1093/ijlct/ctab023
format Article
fullrecord <record><control><sourceid>oup_cross</sourceid><recordid>TN_cdi_crossref_primary_10_1093_ijlct_ctab023</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><oup_id>10.1093/ijlct/ctab023</oup_id><sourcerecordid>10.1093/ijlct/ctab023</sourcerecordid><originalsourceid>FETCH-LOGICAL-c1543-859c7d5140b2602b5c7e43c10eb19ca69105f1a718f61dedacf1bdfb90a3a7433</originalsourceid><addsrcrecordid>eNqFkD1PwzAURS0EEqUwsntkMfWL46YZqwooUiUWWIle_NG4JHFlO0j595S2AxvTu3o69w6HkHvgj8BLMXO7VqWZSljzTFyQCRT5goHI5OWffE1uYtxxLstc8An5XNKYBj1Sb2lqDI1fY-u2TaLKf5uAW0MDJuep9YGiC0z5XrvDozeaYgpu6KLrj83GJ4q9ps3QOU2D2R6geEuuLLbR3J3vlHw8P72v1mzz9vK6Wm6YApkLtpClKrSEnNfZnGe1VIXJhQJuaigVzkvg0gIWsLBz0EajslBrW5ccBRa5EFPCTrsq-BiDsdU-uA7DWAGvfuVURznVWc6Bfzjxftj_g_4ACxVpGA</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype></control><display><type>article</type><title>A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions</title><source>Oxford Journals Open Access Collection</source><source>DOAJ Directory of Open Access Journals</source><source>Elektronische Zeitschriftenbibliothek - Frei zugängliche E-Journals</source><creator>Lou, Siwei ; Huang, Yu ; Xia, Dawei ; Lun, Isaac Y F ; Li, Danny H W</creator><creatorcontrib>Lou, Siwei ; Huang, Yu ; Xia, Dawei ; Lun, Isaac Y F ; Li, Danny H W</creatorcontrib><description>The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy performances of skylight coverage area for the air-conditioned atriums in the hot and humid regions. The energy performance with different atrium heights, glass types and the coverage ratios of the skylight are studied. The daylight performance was simulated by the ray-tracing Radiance and was transferred into EnergyPlus for energy evaluations. The finding suggested that, for hot and humid climates, the skylight coverage ratio should be controlled carefully to prevent the excessive solar heat gain. When the on/off lighting control is applied, the total energy consumption of the single-floor cases (or of the top floor for the multi-floor cases) leveled off when the coverage ratio of the skylight reached 9%. Thus, the skylight is favorable to the energy saving of the low-rise or single-floor commercial buildings only under the current assumptions, as the ground of the atrium cannot be well illuminated while the excessive solar radiation gets into the building. The skylight should be shaded in cooling seasons to prevent the excessive solar heat gains.</description><identifier>ISSN: 1748-1325</identifier><identifier>EISSN: 1748-1325</identifier><identifier>DOI: 10.1093/ijlct/ctab023</identifier><language>eng</language><publisher>Oxford University Press</publisher><ispartof>International journal of low carbon technologies, 2021-09, Vol.16 (3), p.946-955</ispartof><rights>The Author(s) 2021. Published by Oxford University Press. 2021</rights><lds50>peer_reviewed</lds50><oa>free_for_read</oa><woscitedreferencessubscribed>false</woscitedreferencessubscribed><citedby>FETCH-LOGICAL-c1543-859c7d5140b2602b5c7e43c10eb19ca69105f1a718f61dedacf1bdfb90a3a7433</citedby><cites>FETCH-LOGICAL-c1543-859c7d5140b2602b5c7e43c10eb19ca69105f1a718f61dedacf1bdfb90a3a7433</cites></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><link.rule.ids>314,776,780,860,27901,27902</link.rule.ids></links><search><creatorcontrib>Lou, Siwei</creatorcontrib><creatorcontrib>Huang, Yu</creatorcontrib><creatorcontrib>Xia, Dawei</creatorcontrib><creatorcontrib>Lun, Isaac Y F</creatorcontrib><creatorcontrib>Li, Danny H W</creatorcontrib><title>A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions</title><title>International journal of low carbon technologies</title><description>The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy performances of skylight coverage area for the air-conditioned atriums in the hot and humid regions. The energy performance with different atrium heights, glass types and the coverage ratios of the skylight are studied. The daylight performance was simulated by the ray-tracing Radiance and was transferred into EnergyPlus for energy evaluations. The finding suggested that, for hot and humid climates, the skylight coverage ratio should be controlled carefully to prevent the excessive solar heat gain. When the on/off lighting control is applied, the total energy consumption of the single-floor cases (or of the top floor for the multi-floor cases) leveled off when the coverage ratio of the skylight reached 9%. Thus, the skylight is favorable to the energy saving of the low-rise or single-floor commercial buildings only under the current assumptions, as the ground of the atrium cannot be well illuminated while the excessive solar radiation gets into the building. The skylight should be shaded in cooling seasons to prevent the excessive solar heat gains.</description><issn>1748-1325</issn><issn>1748-1325</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2021</creationdate><recordtype>article</recordtype><sourceid>TOX</sourceid><recordid>eNqFkD1PwzAURS0EEqUwsntkMfWL46YZqwooUiUWWIle_NG4JHFlO0j595S2AxvTu3o69w6HkHvgj8BLMXO7VqWZSljzTFyQCRT5goHI5OWffE1uYtxxLstc8An5XNKYBj1Sb2lqDI1fY-u2TaLKf5uAW0MDJuep9YGiC0z5XrvDozeaYgpu6KLrj83GJ4q9ps3QOU2D2R6geEuuLLbR3J3vlHw8P72v1mzz9vK6Wm6YApkLtpClKrSEnNfZnGe1VIXJhQJuaigVzkvg0gIWsLBz0EajslBrW5ccBRa5EFPCTrsq-BiDsdU-uA7DWAGvfuVURznVWc6Bfzjxftj_g_4ACxVpGA</recordid><startdate>20210929</startdate><enddate>20210929</enddate><creator>Lou, Siwei</creator><creator>Huang, Yu</creator><creator>Xia, Dawei</creator><creator>Lun, Isaac Y F</creator><creator>Li, Danny H W</creator><general>Oxford University Press</general><scope>TOX</scope><scope>AAYXX</scope><scope>CITATION</scope></search><sort><creationdate>20210929</creationdate><title>A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions</title><author>Lou, Siwei ; Huang, Yu ; Xia, Dawei ; Lun, Isaac Y F ; Li, Danny H W</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-c1543-859c7d5140b2602b5c7e43c10eb19ca69105f1a718f61dedacf1bdfb90a3a7433</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2021</creationdate><toplevel>peer_reviewed</toplevel><toplevel>online_resources</toplevel><creatorcontrib>Lou, Siwei</creatorcontrib><creatorcontrib>Huang, Yu</creatorcontrib><creatorcontrib>Xia, Dawei</creatorcontrib><creatorcontrib>Lun, Isaac Y F</creatorcontrib><creatorcontrib>Li, Danny H W</creatorcontrib><collection>Oxford Journals Open Access Collection</collection><collection>CrossRef</collection><jtitle>International journal of low carbon technologies</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>Lou, Siwei</au><au>Huang, Yu</au><au>Xia, Dawei</au><au>Lun, Isaac Y F</au><au>Li, Danny H W</au><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions</atitle><jtitle>International journal of low carbon technologies</jtitle><date>2021-09-29</date><risdate>2021</risdate><volume>16</volume><issue>3</issue><spage>946</spage><epage>955</epage><pages>946-955</pages><issn>1748-1325</issn><eissn>1748-1325</eissn><abstract>The skylight on the roof of an atrium can be popular for commercial malls to illuminate the core area of the building. However, the solar radiation and its heat can get into the building together with the daylight, causing excessive cooling load. This paper studies the daylighting and energy performances of skylight coverage area for the air-conditioned atriums in the hot and humid regions. The energy performance with different atrium heights, glass types and the coverage ratios of the skylight are studied. The daylight performance was simulated by the ray-tracing Radiance and was transferred into EnergyPlus for energy evaluations. The finding suggested that, for hot and humid climates, the skylight coverage ratio should be controlled carefully to prevent the excessive solar heat gain. When the on/off lighting control is applied, the total energy consumption of the single-floor cases (or of the top floor for the multi-floor cases) leveled off when the coverage ratio of the skylight reached 9%. Thus, the skylight is favorable to the energy saving of the low-rise or single-floor commercial buildings only under the current assumptions, as the ground of the atrium cannot be well illuminated while the excessive solar radiation gets into the building. The skylight should be shaded in cooling seasons to prevent the excessive solar heat gains.</abstract><pub>Oxford University Press</pub><doi>10.1093/ijlct/ctab023</doi><tpages>10</tpages><oa>free_for_read</oa></addata></record>
fulltext fulltext
identifier ISSN: 1748-1325
ispartof International journal of low carbon technologies, 2021-09, Vol.16 (3), p.946-955
issn 1748-1325
1748-1325
language eng
recordid cdi_crossref_primary_10_1093_ijlct_ctab023
source Oxford Journals Open Access Collection; DOAJ Directory of Open Access Journals; Elektronische Zeitschriftenbibliothek - Frei zugängliche E-Journals
title A study of the skylight coverage ratio for air-conditioned atriumsin the hot and humid regions
url https://sfx.bib-bvb.de/sfx_tum?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-02-09T02%3A29%3A42IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-oup_cross&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=A%20study%20of%20the%20skylight%20coverage%20ratio%20for%20air-conditioned%20atriumsin%20the%20hot%20and%20humid%20regions&rft.jtitle=International%20journal%20of%20low%20carbon%20technologies&rft.au=Lou,%20Siwei&rft.date=2021-09-29&rft.volume=16&rft.issue=3&rft.spage=946&rft.epage=955&rft.pages=946-955&rft.issn=1748-1325&rft.eissn=1748-1325&rft_id=info:doi/10.1093/ijlct/ctab023&rft_dat=%3Coup_cross%3E10.1093/ijlct/ctab023%3C/oup_cross%3E%3Curl%3E%3C/url%3E&disable_directlink=true&sfx.directlink=off&sfx.report_link=0&rft_id=info:oai/&rft_id=info:pmid/&rft_oup_id=10.1093/ijlct/ctab023&rfr_iscdi=true